260
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
5.7
H: Terminal Functions
H parameters
are used to assign functions to external input and output terminals.
◆
H1: Digital Inputs
H1 Parameters
set the MFDI terminal functions.
■
H1-01 to H1-07 Terminal S1 to S7 Function Selection
The drive has 7 MFDI terminals. Refer to
for drive default settings and functions.
Table 5.36 MFDI Default Settings and Functions
No.
Name
Default
Function
H1-01
Terminal S1 Function Selection
40
Forward RUN (2-Wire)
H1-02
Terminal S2 Function Selection
F
Not Used
H1-03
Terminal S3 Function Selection
24
External Fault (NO-Always-Coast)
H1-04
Terminal S4 Function Selection
14
Fault Reset
H1-05
Terminal S5 Function Selection
3
Multi-Step Speed Reference 1
H1-06
Terminal S6 Function Selection
4
Multi-Step Speed Reference 2
H1-07
Terminal S7 Function Selection
6
Jog Reference Selection
Table 5.37 MFDI Setting Values
Setting Value
Function
Reference
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog Reference Selection
7
Accel/Decel Time Selection 1
8
Baseblock Command (N.O.)
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
B
Overheat Alarm (oH2)
C
Analog Terminal Enable Selection
F
Not Used
14
Fault Reset Procedure
15
Fast Stop (N.O.)
17
Fast Stop (N.C.)
18
Timer Function
19
PID Disable
1B
Programming Lockout
1E
Reference Sample Hold
20 to 2F
External Fault
30
PID Integrator Reset
31
PID Integrator Hold
34
PID Soft Starter Disable
35
PID Input (Error) Invert
3E
PID Setpoint Selection 1
Setting Value
Function
Reference
3F
PID Setpoint Selections 2
40
Forward RUN (2-Wire)
44
Add Offset Frequency 1 (d7-01)
45
Add Offset Frequency 2 (d7-02)
46
Add Offset Frequency 3 (d7-03)
51
Sequence Timer Disable
52
Sequence Timer Cancel
61
Speed Search from Fmax
62
Speed Search from Fref
63
Field Weakening
68
High Slip Braking (HSB) Activate
6A
Drive Enable
70
Drive Enable 2
82
PI Switch to Aux
83
Dedicated Multi-Setpoint YA-02
84
Dedicated Multi-Setpoint YA-03
85
Dedicated Multi-Setpoint YA-04
88
Thermostat Fault
A8
PI2 Control Disable
AA
PI2 Control Inverse Operation
AB
PI2 Control Integral Reset
AC
PI2 Control Integral Hold
AD
Select PI2 Control PI Parameters
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...