YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
271
■
51: Sequence Timer Disable
Setting Value
Function
Description
51
Sequence Timer Disable
Sets the command to disable Sequence Timers.
ON : Sequence Timer is Disabled
The drive ignores Sequence Timers and operates as usual as specified by
b1-02 [Run Command Selection 1]
.
■
52: Sequence Timer Cancel
Setting Value
Function
Description
52
Sequence Timer Cancel
Sets the command to cancel the currently active Sequence Timer.
ON : Cancel Active Sequence Timer
Operation will continue with the next scheduled sequence timer. When you cancel the sequence timer before you
cycle the Run command, it will enable the sequence timer again.
■
61: Speed Search from Fmax
Setting Value
Function
Description
61
Speed Search from Fmax
Sets the function to start speed search using an external reference although
b3-01 = 0 [Speed Search Selection at Start = Disabled]
.
When the terminal is turned ON for
b3-24 = 2 [Speed Search Method Selection = Current Detection 2]
, the drive
starts speed search from the maximum output frequency.
Note:
•
The drive will detect
oPE03 [Multi-Function Input Setting Err]
when
H1-xx = 61 and 62
are set at the same time.
•
Refer to
“
b3: Speed Search
”
for more information.
■
62: Speed Search from Fref
Setting Value
Function
Description
62
Speed Search from Fref
Sets the function to use an external reference to start speed search although
b3-01 = 0 [Speed Search Selection at Start = Disabled]
.
When the terminal is turned ON for
b3-24 = 2 [Speed Search Method Selection = Current Detection 2]
, the drive
starts speed search from the frequency reference.
Note:
•
The drive will detect
oPE03 [Multi-Function Input Setting Err]
when
H1-xx = 61 and 62
are set at the same time.
•
Refer to
“
b3: Speed Search
”
for more information.
■
63: Field Weakening
Setting Value
Function
Description
63
Field Weakening
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in
d6-01 [Field
Weakening Level] and d6-02 [Field Weakening Frequency Limit]
when the input terminal is activated.
Note:
Refer to
d6: Field Weakening on page 241
for more information.
■
68: High Slip Braking (HSB) Activate
Setting Value
Function
Description
68
High Slip Braking (HSB)
Activate
Sets the command to use high-slip braking to stop the motor.
Note:
•
When you restart the drive after you use high-slip braking, make sure that the drive fully stops the motor then clear the high-slip braking
input.
•
Refer to
“
n3: High Slip/Overex Braking
”
for more information.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...