YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
657
9.16
Y: Application Features
◆
Y1: Application Basics
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
Y1-04
(3C03)
RUN
Sleep Wake-up Level
Sets the level that feedback must be less than for the time set in
Y1-05 [Sleep Wake-up
Level Delay Time]
to start the system. This level also sets the wake up level when the drive
is in Sleep Mode. When
Y1-04 < 0
, the feedback level must decrease this amount to less
than the setpoint.
Note:
•
When PID operates in reverse mode, the feedback value must increase to more than
the start level for the time set in
Y1-05
for the system to start.
•
When
Y2-01 = 5 [Sleep Level Type = Output Frequency (non-PID)]
, the drive will
ignore this parameter.
•
Set this parameter to 0.0 to disable the function.
•
Range is 0.00 to 99.99 with sign-bit
“
-
”
or
“
+
”
indicating Delta to Setpoint.
•
Display unit and scaling change when the system units change.
0.0
(-999.9 - +999.9)
Y1-05
(3C04)
RUN
Sleep Wake-up Level
Delay Time
Sets the drive to start the System again when the feedback decreases to less than
Y1-04
[Sleep Wake-up Level]
for the time set in this parameter.
1 s
(0 - 3600 s)
Y1-06
(3C05)
RUN
Minimum Speed
Sets the minimum frequency at which the drive will run. The drive applies this setting to
HAND and AUTO modes.
Note:
The unit, decimal place, and setting range change when the
Y1-07 [Minimum Speed
Units]
setting changes:
•
Y1-07 = 0 [Hz]
: The setting range is 0.0 Hz to
E1-04
Hz.
•
Y1-07 = 1 [RPM]
: The setting range is 0 RPM to (
E1-04
× 60) RPM.
0.0 Hz
Determined by Y1-07
Y1-07
(3C06)
Minimum Speed Units
Sets the units and decimal place for
Y1-06 [Minimum Speed]
.
0 : Hz
1 : RPM
Note:
Changing
Y1-07
will set
Y1-06 [Minimum Speed]
to the default value.
0
(0, 1)
Y1-08
(3C07)
RUN
Low Feedback Level
Sets the lower detection level for the PID feedback.
Note:
•
Unit and decimal place change when the system units change.
•
Range is 0.00 to 99.99 with sign-bit
“
-
”
indicating Delta to Setpoint.
0.00%
(0.00 - 99.99%)
Y1-09
(3C08)
RUN
Low Feedback Lvl Fault
Dly Time
Sets the delay time for the drive to detect an
LFB [Low Feedback Sensed]
fault after the
feedback level decreases to less than the value set in
Y1-08 [Low Feedback Level]
.
Note:
Set
Y1-10 = 0 [Low Feedback Selection = Fault (and Digital Output)]
to enable this
parameter.
10 s
(0 - 3600 s)
Y1-10
(3C09)
Low Feedback Selection
Sets the drive response when the feedback decreases to less than
Y1-08 [Low Feedback
Level]
for longer than the time set in
Y1-09 [Low Feedback Lvl Fault Dly Time]
.
0 : Fault (and Digital Output)
1 : Alarm (and Digital Output)
2 : Digital Output Only
0
(0 - 2)
Y1-11
(3C0A)
RUN
High Feedback Level
Sets the upper detection level for the PID feedback.
Note:
•
Unit and decimal place change when the system units change.
•
Range is 0.00 to 99.99 with sign-bit
“
+
”
indicating Delta to Setpoint.
0.00%
(0.00 - 99.99%)
Y1-12
(3C0B)
RUN
High Feedback Lvl Fault
Dly Time
Sets the delay time between when the drive detects high feedback until the drive faults on
an
HFB [High Feedback Sensed]
fault.
Note:
This parameter is effective only when
Y1-13 = 0 [High Feedback Selection = Fault
(and Digital Output)]
.
5 s
(0 - 3600 s)
Y1-13
(3C0C)
High Feedback Selection
Sets the drive response when the feedback increased to more than
Y1-11 [High Feedback
Level]
for longer than the time set in
Y1-12 [High Feedback Lvl Fault Dly Time]
.
0 : Fault (and Digital Output)
1 : Alarm (and Digital Output)
2 : Digital Output Only
0
(0 - 2)
Y1-14
(3C0D)
RUN
Feedback Hysteresis
Level
Sets the hysteresis level for low and high level feedback detection.
Note:
Unit and decimal place change when the system units change.
0.0%
(0.0 - 10.00%)
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...