5.1 A: Initialization Parameters
174
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
5.1
A: Initialization Parameters
A parameters [Initialization Parameters]
set the operating environment and operating conditions for the drive.
◆
A1: Initialization
A1 parameters
set the operating environment and operating conditions. For example, these parameters set the keypad
language and the parameter access level.
■
A1-00: Language Selection
No.
(Hex.)
Name
Description
Default
(Range)
A1-00
(0100)
RUN
Language Selection
Sets the language for the HOA keypad.
0
(0, 5)
Note:
When you initialize the drive with parameter
A1-03 [Initialize Parameters]
, the drive will not reset this parameter.
0 : English
5 : Spanish
■
A1-01: Access Level Selection
No.
(Hex.)
Name
Description
Default
(Range)
A1-01
(0101)
RUN
Access Level Selection
Sets user access to parameters. The access level controls which parameters the keypad will display
and which parameters you can set.
2
(0 - 4)
0 : Operation Only
Access to
A1-00 [Language Selection]
,
A1-01
,
A1-04 [Password]
, and the
U Monitors
.
1 : User Parameters
Access to
A1-00
,
A1-01
,
A1-04
, and parameters registered to
A2-01 to A2-32 [User Parameters 1 to 32]
.
2 : Advanced Level
Access to all parameters, but not Expert Mode parameters.
3 : Expert Level
Access to all parameters including Expert Mode parameters.
4 : Lock Parameters
Parameters that you can see are the same as
Advanced Level
, but parameters that you can change are only
A1-01
and
A1-04
.
The keypad will show the message
[Parameters Locked]
:
•
In the HOME screen, the keypad will show the message
[Parameters Locked]
on the second line.
•
If you try to change a parameter setting, the keypad will show the warning
[LOCK] [Parameters Locked]
for 2 s.
To clear this warning, push one of the keys on the keypad.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...