72
Technical Handbook
Pushbuttons
Function
MODE UP
MODE DOWN
OFF/RESET
PROGRAM
The generator is disabled; warnings and alarms are cancelled.
You can program the parameters.
MAN
(Manual)
The controller is set for manual gen-set control.
Press the
START
button to start the engine.
Press the
STOP
button to stop the engine.
With the engine running and up to speed, press the
GCB
button for manual
opening/closing of the GCB circuit breaker.
From display pages M.02…M.04, press
SHIFT+GCB
buttons for manual
opening/closing of the BCB circuit breaker
From display page M.09, press
SHIFT+GCB
buttons for manual
opening/closing of the LCB circuit breaker
From display pages M.10…M.12, press
SHIFT+GCB
buttons for manual
opening/closing of the ACB circuit breaker
AUTO
(Automatic)
TEST
The controller is set for the automatic generator control, which will be started
when a charge procedure is needed for the plant battery and, optionally, if the
loads are unsupplied.
By pressing the
START
button, it is possible to activate/deactivate the TEST
mode. This, unless configured differently, does not close the GCB circuit
breaker.
The
STOP
button, unless configured otherwise, causes the stop of the
generator (if running) and the activation of a block.
ESC/SHIFT
In programming mode, it cancels the changes made to a variable value, brings
up the previous menu level, or exits programming mode. If it is pressed for at
least two seconds in any menu, you exit the programming mode retaining the
current menu position for further programming access.
When pressed in any menu, it displays on the upper line the engine status.
In OFF/RESET mode and depending on the selected page, if pressed
together with the
ENTER
button for at least 5 seconds, it can reset counters
to zero, reload default values of the programming parameters or cancel the
history logs (in the version equipped with CAN-BUS, it allows to force exit from
BUS OFF
mode). When used during the keyboard regulation function, it
aborts the function.
Used together with
ACK
button, it resets the anomalies.
Used together with
GCB
button, depending on the page shown it opens/closes
the ACB, BCB or LCB circuit breakers (in MAN mode).