Technical Handbook 195
P.0421
Generator enable days.
P.0422
Generator enable start time.
P.0423
Generator enable stop time.
P.0426
Days for remote start.
P.0438
Interval of days for maintenance.
To disable:
Set the clock
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This warning is always enabled. It is activated if the controller detects a not-valid clock status,
and functions using the clock are set, such as the weekly test (P.0420), operation enabling
time (P.0421, P.0422, P.0423), generator start forced (P.0426) and days to next maintenance
(P.0438). To deactivate it, you need to set the clock.
Type:
Warning
Related parameters:
P.0105
Nominal frequency.
P.0133
Engine's nominal speed (primary).
P.0134
Engine's nominal speed (secondary).
P.0395
Low frequency threshold.
P.0396
Low frequency delay.
To disable:
P.0396 = 0
Enabled in:
*
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection works on the generator frequency if the AC voltages have been connected,
Otherwise, if possible, it works on the engine speed. It is only enabled if the engine has been
started by the controller (if the command for the fuel solenoid is activated) and it is disabled
during the crank/stop cycles. It is enabled the first time (from engine start) the generator's
voltages and frequency/speed enter the tolerance range (see generator sequence
description). In MAN it is only enabled if the GCB breaker is closed. It is activated if, under the
conditions previously mentioned, the generator frequency (or the engine speed) is
continuously below the threshold P.0395 for the time P.0396.
In MAN it is only enabled if the GCB breaker is closed, or if the bit 2 of the parameter P.0249
is set to
“1”.
Type:
Warning
Related parameters:
P.0102
Nominal voltage (AC) of the generator.
P.9641
Nominal voltage (DC).
P.0202
Hysteresis for generator's measures.
P.0393
High voltage threshold.
P.0394
High voltage delay.
To disable:
P.0394 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection, when possible, works on the DC voltage of the generator. If not possible (GCB
closed), if AC voltages are available it works with them,
otherwise it will never be activated.
The protection is only enabled if the engine has been started by the controller (if the command
for the fuel solenoid is activated) and it is disabled during the crank/stop cycles. It is activated
if, under the conditions previously mentioned, the DC voltage of the generator or at least one
of the AC voltages exceeds continuously the threshold P.0393 for the time P.0394.