Technical Handbook 89
For HS315
Link
controllers (equipped with GPRS internal module), the controller shows:
•
The IP address assigned to the controller by the GPRS network.
Some useful information for the
connection to “Si.Mo.Ne server.”:
o
Controller name
o
Latitude and Longitude acquired by the
GNSS
module or set through the
parameters of the controller. This information flashes if the
GNS
S module is
not able to set the position.
o
The
HDOP
(Horizontal Diluition Of Precision) value: it is a precision indicator
(the lower it is, the sharper the position).
o
the number of satellites that are "view" by the
GNSS
module (when searching
for coordinates) or the number of satellites used for the "
FIX
" of the
coordinates (once the correct position has been determined).
The S.05 (CAN-BUS) page displays the engine CAN-BUS communication status. This page
shows the communication status of the bus. There are three possible indications:
•
ERROR-ACTIVE: normal operation.
•
ERROR-PASSIVE: communication is working despite faults (errors).
•
BUS-OFF: Gen-set has interrupted the connection to the bus due to too many errors.
The controller shows also the transmission / reception error counters, both current and
maximum values. By pressing the ACK/ENTER + ESC/SHIFT buttons for five seconds, you
can force the CAN
– controller to exit from BUS-OFF status and clear the error counters.
Page S.06 (BOARD) is dedicated to the HS315 and contains:
•
The language currently used by the device and allows you to select between the ones
installed (see par. 8.6)
•
Current date and time in long format (flashing if the clock is not valid)
•
The unambiguous serial number of the controller board (called ID CODE).
•
The code of the software currently loaded on the controller board (see par. 1.7).
Pages S.07, S.08 and S.09 (GENERIC STATUS 1,2,3) are used to show the generic statuses
acquired by digital inputs configured with the following functions:
•
DIF.3201, DIF.3202: page S.07
•
DIF.3203, DIF.3204: page S.08
•
DIF.3205, DIF.3205: page S.09
The activation of a digital input configured with the function DIF.3202, DIF.3204 or DIF.3206
forces the display to show the related page (it is an “important status”, the operator must be
informed immediately).
The controller uses one row per each status: on the left a description is shown (configured by
means
the parameters related to the input) and on the right the logical status of the input (“1”
or “0”). If the page contains more than six statuses, the controller shows all them by rotation
(every 2 seconds, keep pressed the SHIFT button to stop the rotation).
These pages are hidden if there are no statuses to be shown.
Page S10 (FUEL PUMP) is available only if at least one outlet is configured for managing the
fuel pump. Contains the following information: