96
Technical Handbook
This page is shown only if the controller is configured to acquire the AC voltages of the auxiliary
source. It is also hidden if the neutral of the generator is not connected to the controller (P.9618
different from “018”). It shows the three line-to-neutral voltages, with their phases sequence
(CW / CCW).
In the bottom-right corner, the symbol of the auxiliary source is shown. This allow the operator
to immediately understand that he/she is looking at auxiliary source measurements (there are
very similar pages related to other sources).
This page allows the operator to manually modify the value of the analogue output connected
to the voltage or speed regulator. The operation should be done with GCB circuit breaker
opened, otherwise the control loops that manage the charge process will probably cancel the
manual modifications.
On the last row, the controller shows
the “base” value for the analogue output (the control
loops will “move” the value around this “base” value). To change it, you must:
•
Press the ACK/ENTER button.
•
Modify the value using the vertical arrows.
•
Confirm with the ACK/ENTER button.
On the top of the page, the engine speed and the generator DC voltage are shown to allow
the operator to verify the effects of the modification.
This page is only shown if some electronic batteries are properly configured. It displays the
whole battery set values (replaced by dashes if not available):
•
Average batteries voltage.
•
Total batteries charge/discharge current.
•
Total batteries charge level.
•
Average batteries temperature.
This page is only shown if some electronic batteries are properly configured.
It shows values related to one of the connected batteries. It is possible to select a different
module by pressing the
ACK/ENTER
button and using vertical arrows (confirm with
ACK/ENTER
). It shows the following values (replaced by dashes if not available):
•
Voltage.
•
Charge/discharge current.
•
Charge level.
•
Average temperature.
This page is only shown if some electronic batteries are properly configured.
It shows values related to one of the connected batteries. It is possible to select a different
module by pressing the
ACK/ENTER
button and using vertical arrows (confirm with
ACK/ENTER
). It shows the following values (replaced by dashes if not available):