Technical Handbook 131
•
One warning for low frequency (W058, parameters P.0202, P.0395, P.0396).
•
One warning for high frequency (W060, parameters P.0202, P.0397, P.0398).
•
One alarm (block) for maximum frequency (A004, parameters P.0202, P.0307,
P.0308).
HS315 implements 4 different protections for the generator voltage. They can work with both
AC and DC voltages. DC voltage has higher priority, but it cannot be used when another active
source (plant battery or auxiliary source) is connected to the generator.
•
One deactivation for minimum voltage (D001, parameters P.0202, P.0301, P.0302).
•
One warning for low voltage (W056, parameters P.0202, P.0391, P.0392).
•
One warning for high voltage (W059, parameters P.0202, P.0393, P.0394).
•
One alarm (block) for maximum voltage (A002, parameters P.0202, P.0303, P.0304).
HS315 opens the GCB in case of alarms (blocks) and deactivations (D001, A002, D003, A004,
A006, A011, A016) (in MAN the deactivations D001 and D003 are managed only when GCB
is closed).