Technical Handbook 187
Override:
Engine.
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the minimum fuel level contact of the float (function DIF.4211 -
“Minimum fuel level”)
(in parameter P.2001 or equivalent for the other inputs) and if a time other than zero has been
set for said input (parameter P.2002 or equivalent). It is activated if the configured input
remains continuously active for the associated time.
Type:
Alarm
Related parameters:
P.4009
Function of the analogue input 2 (JQ) or equivalent for the other
inputs.
P.0347
Minimum fuel level threshold.
P.0348
Minimum fuel level delay.
P.0700
Engine type.
To disable:
P.0348 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
Engine.
This protection is enabled if the controller acquires the measurement of the fuel level (directly
from the ECU of the engine or if one of the analogue inputs of the controller is configured to
acquire such measure - function AIF.1220 or AIF.1221 in parameter P.4009 or equivalent for
the other inputs) and if a time other than zero has been set for the protection (parameter
P.0348). It is activated if the level measure remains continuously below or equal to threshold
P.0347 (in percentage) for time P.0348.
Type:
Warning
Related parameters:
P.2001
Function of the input 01 or equivalent for the other inputs.
P.2002
Delay for the input 01 or equivalent for the other inputs.
To disable:
P.2002 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the minimum fuel level contact of the float (function DIF.4212 -
“Low fuel level”) (in
parameter P.2001 or equivalent for the other inputs) and if a time other than zero has been
set for said input (parameter P.2002 or equivalent). It is activated if the configured input
remains continuously active for the associated time.
Type:
Warning
Related parameters:
P.4009
Function of the analogue input 2 (JQ) or equivalent for the other
inputs.
P.0345
Low fuel level threshold.
P.0346
Low fuel level delay.
P.0700
Engine type.
To disable:
P.0346 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled if the controller acquires the measurement of the fuel level (directly
from the ECU of the engine or if one of the analogue inputs of the controller is configured to
acquire such measure - function AIF.1220 or AIF.1221 in parameter P.4009 or equivalent for
the other inputs) and if a time other than zero has been set for the protection (parameter