202
Technical Handbook
Related parameters:
P.2001
Function of the input 01 or equivalent for the other inputs
P.2002
Delay for the input 01 or equivalent for the other inputs.
To disable:
P.2002 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the external contact that signals the trip of the over current protection of the circuit
breaker (function DIF.3012 -
“Trip of ACB circuit breaker”) (in parameter P.2001 or equivalent
for the other inputs) and if a time other than zero has been set for said input (parameter P.2002
or equivalent). It activates if the configured input remains continuously active for the associated
time.
Type:
Warning
Related parameters:
P.9636
Function for terminal JP.
P.9662
Voltage compensation due to temperature.
P.9663
Charge current compensation due to temperature.
To disable:
-
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled if JP terminals are enabled (P.9636 <> 0). It is activated if the
resistance measurement on the JP terminals is greater than 333 Ohm ("broken wire").
Moreover, it is enabled if it is required the compensation of the voltage and current thresholds
for the plant battery related to the plant battery temperature. It is activated if the measure of
the plant battery temperature is not available because the PT100 sensor is not properly
connected to the JP terminals.
Type:
Latched warning
Related parameters:
P.9701
Battery temperature hysteresis.
P.9702
Min battery temperature threshold.
P.9703
Min battery temperature delay.
To disable:
P.9702 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is activated if the measure of the plant battery temperature remains
continuously below to threshold P.9702 for time P.9703.
Type:
Warning
Related parameters:
P.9701
Battery temperature hysteresis.
P.9704
Low battery temperature threshold.
P.9705
Low battery temperature delay.
To disable:
P.9705 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is activated if the measure of the plant battery temperature remains
continuously below to threshold P.9704 for time P.9705.