188
Technical Handbook
P.0346). It is activated if the level measure remains continuously below or equal to threshold
P.0345 (in percentage) for time P.0346.
Type:
Warning
Related parameters:
P.2001
Function of the input 01 or equivalent for the other inputs.
P.2002
Delay for the input 01 or equivalent for the other inputs.
To disable:
P.2002 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the minimum fuel level contact of the float (function DIF.4213 -
“High fuel level”) (in
parameter P.2001 or equivalent for the other inputs) and if a time other than zero has been
set for said input (parameter P.2002 or equivalent). It is activated if the configured input
remains continuously active for the associated time.
Type:
Warning
Related parameters:
P.4009
Function of the analogue input 2 (JQ) or equivalent for the other
inputs.
P.0343
High fuel level threshold.
P.0344
High fuel level delay.
P.0700
Engine type.
To disable:
P.0344 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled if the controller acquires the measurement of the fuel level (directly
from the ECU of the engine or if one of the analogue inputs of the controller is configured to
acquire such measure - function AIF.1220 or AIF.1221 in parameter P.4009 or equivalent for
the other inputs) and if a time other than zero has been set for the protection (parameter
P.0344). It is activated if the level measure remains continuously above or equal to threshold
P.0343 (in percentage) for time P.0344.
Type:
Warning
Related parameters:
P.2001
Function of the input 01 or equivalent for the other inputs.
P.2002
Delay for the input 01 or equivalent for the other inputs.
P.0216
Time mask for engine protections.
To disable:
P.2002 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the external high coolant temperature contact (function DIF.4231 -
“High coolant
temperature
”) (in parameter P.2001 or equivalent for the other inputs) and if a time other than
zero has been set for said input (parameter P.2002 or equivalent). It is only enabled if the
engine has been started by the controller (if the command for the fuel solenoid is activated)
and is disabled in the engine start/stop phases. It activates if the input configured is
continuously “active” for the time configured, but only after the time P.0216 (oil mask) from
engine start has elapsed (this is to allow you to start the engine idle, to cool it off).