Technical Handbook 75
Indicates that the CAN-BUS has been disabled (no expansion
modules nor ECU interface connected), or that the controller is
not receiving any messages from the ECU of the engine.
AUC DC
SOURCE
The auxiliary source voltage (DC, AC, or from digital input) is
present and stable in the tolerance range.
The auxiliary source voltage (DC, AC, or from digital input) is not
present.
Flashes at 50% on: during transition between the previous two
states.
Flashing at 25% on: the auxiliary source voltage (DC, AC, or from
digital input) is present but below the tolerance range.
Flashing at 75% on: the auxiliary source voltage (DC, AC, or from
digital input) is present but over the tolerance range.
GENERATOR
LIVE
The generator voltage (DC or AC) is present and stead within the
tolerance range.
The generator voltage (DC or AC) is not present.
Flashes at 50% on: during transition between the previous two
states.
Flashing at 25% on: the generator voltage (DC or AC) is present
but below the tolerance range, or it is absent but the engine is
running.
Flashing at 75% on: the generator voltage (DC or AC) is present
but over the tolerance range.
GCB
The circuit breaker is opened.
The circuit breaker is closed.
Flashes at 25% on: the circuit breaker is opened with closure
command activated.
Flashing at 75% on: the circuit breaker is closed with opening
command activated.
LOAD
DC voltage is present on the LOADS.
DC voltage is not present on the LOADS.
BCB
The circuit breaker is opened.
The circuit breaker is closed.
Flashes at 25% on: the circuit breaker is opened with closure
command activated.
Flashing at 75% on: the circuit breaker is closed with opening
command activated.
PLANT
BATTERY
The voltage of the plant battery is present and in the tolerance
range.
The voltage of the plant battery is not present.
Flashing at 25% on: the voltage of the plant battery is present but
below the tolerance range.
Flashing at 75% on: the voltage of the plant battery is present but
over the tolerance range.
By pressing the STOP button when the controller is in OFF/RESET mode, the controller
switches on all the indicators (“lamp test”) to allow their check by the operator. In this phase