Technical Handbook 201
To disable:
bit 14 of P.0704 on
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only if the board is connected to the engine via the CAN BUS
(P.0700 different from zero). It is activated when the engine signals the active state of its yellow
lamp over the CAN BUS.
Type:
Configurable
Related parameters:
P.0700
Engine type.
P.0704
Can-Bus alarms disable mask.
To disable:
bit 15 of P.0704 on
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
Engine.
This protection is enabled only if the board is connected to the engine via the CAN BUS
(P.0700 different from zero). It is activated when the engine signals the active state of its red
lamp over the CAN BUS. Using bit 13 of P.0704 it is possible to configure the protection as
warning or alarm.
Type:
Latched warning
Related parameters:
P.2001
Function of the input 01 or equivalent for the other inputs
P.2002
Delay for the input 01 or equivalent for the other inputs.
To disable:
P.2002 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the external contact that signals the trip of the over current protection of the circuit
breaker (function DIF.3016 -
“Trip of BCB circuit breaker”) (in parameter P.2001 or equivalent
for the other inputs) and if a time other than zero has been set for said input (parameter P.2002
or equivalent). It activates if the configured input remains continuously active for the associated
time.
Type:
Latched warning
Related parameters:
P.2001
Function of the input 01 or equivalent for the other inputs
P.2002
Delay for the input 01 or equivalent for the other inputs.
To disable:
P.2002 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the external contact that signals the trip of the over current protection of the circuit
breaker (function DIF.3017 -
“Trip of LCB circuit breaker”) (in parameter P.2001 or equivalent
for the other inputs) and if a time other than zero has been set for said input (parameter P.2002
or equivalent). It activates if the configured input remains continuously active for the associated
time.
Type:
Latched warning