214
Technical Handbook
parameters.
Remark: if engine’s protections override function is enabled, this anomaly
becomes a warning.
See [1] to check the correspondence between alarm code and analogue input.
Type:
Warning
Related parameters:
-
To disable:
-
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
The protection is enabled only when a valid PLC program has been transferred to the board.
It reports possible problems during the running of the PLC:
•
The PLC program uses more FLASH memory than available.
•
The PLC program uses more RAM memory than available.
•
The PLC program has an invalid control check-sum.
•
The PLC program is developed with a version not supported by this board.
•
A digital or analogue output controlled by the PLC is not configured with DOF.0101 or
AOF.0101
function (“used by the PLC”).
•
The PLC program uses a resource (of any kind) not available on this board (for
example, a digital input of a non-connected expansion module).
•
An invalid parameter has been specified for one of PLC blocks.
•
An invalid type of block has been specified.
•
Calculation error during the running of the program.
On S.02 page, by selecting this early warning, the board shows additional information to help
solving the problem.
The PLC program, through one of its blocks, can activate anomalies. 901 through 964 codes
are connected to such anomalies. Anomalies triggered by the PLC can be shutdowns,
deactivations, warnings or latched warnings.