22
Technical Handbook
DIF.2063
Full override of protections.
When the input is activated, all the protections (except for few,
see [1] ) which involve alarms or deactivations become
warnings.
DIF.2064
Override generator’s protections.
When the input is “active”, all the protections for the generator,
which normally act as alarms or deactivation become mere
warnings
DIF.2071
Inhibit DPF regeneration.
When the input is "active", the controller "prevents" the
regeneration of the particulate filter to the engine ECU. See
par. 8.5.5.8.
DIF.2072
Force DPF regeneration.
When the input is "active", the controller requires the
regeneration of the particulate filter to the engine ECU. See
par. 8.5.5.8.
DIF.2241
Fuel pump in MAN-OFF mode.
When the input is active, the mode of the fuel pump is forced
into “Manual-OFF”.
DIF.2242
Fuel pump in MAN-ON mode.
When the input is active, the mode of the fuel pump is forced
into “Manual-ON”.
DIF.2243
Fuel pump in AUTO mode.
When the input is active, the mode of the fuel pump is forced
into “Automatic”.
DIF.2271
Remote OFF.
When this input is active, the operation mode of the controller
is forced into OFF-RESET and you cannot use the buttons on
the panel to change it.
NB: when this input is deactivated, if
there are no inputs configured with the functions DIF.2272
and DIF.2273, the operation mode returns to what it was
prior to the activation of the input
DIF.2272
Remote MAN.
When this input is active, the operation mode of the controller
is forced into MAN and you cannot use the buttons on the panel
to change it.
DIF.2273
Remote AUTO.
When this input is active, the operation mode of the controller
is forced into AUTO and you cannot use the buttons on the
panel to change it.
DIF.2321
Full charge.
When this input is active during a charge cycle, the controller
performs a full charge (thus using the setpoints of the menu
2.5.2 instead of the ones of the menu 2.5.3).
DIF.2501
Inhibition of start.
When the input is
“active”, the automatic start of the engine is
inhibited. The “REMOTE START” mode is not influenced by
this function.
DIF.2502
Inhibition of supply.
In automatic mode, when this input is “active”, the controller
opens GCB (but only if it can be re-closed, thus if a closure
command is configured).
DIF.2701
Enables remote start requests.
If this function
is defined for one input, “REMOTE START”
function is inhibited if the input is not active.
DIF.2705
Disables
protections
on
analogue
measures.
When this input is “activated”, the thresholds set on analogue
measures having bit 13 ON in the third configuration parameter
(see par. 5.6.2) do not trigger the relevant protections.
DIF.2706
Enables the commands by the serial ports.
If this input is not active, the controls sent via Modbus
HOLDING REGISTER 101 and 102 are not accepted.
DIF.2709
Consent to start.
In case of a request for automatic starting, the board activates
its internal sequence to start the engine, but it does not activate
any actual control until this input (if it exists) is activated (it can
be used, for example, to manage pre-ventilation).
DIF.3001
Status of GCB circuit breaker.
YES
It is used to detect the actual status of the KM/MCB circuit
breaker. In case of discordance between status and command,
a signalling will outline it.
DIF.3002
Status of ACB circuit breaker.
YES
It is used to detect the actual status of the KM/MCB circuit
breaker. In case of discordance between status and command,
a signalling will outline it.
DIF.3003
Status of BCB circuit breaker.
YES
It is used to detect the actual status of the KM/MCB circuit
breaker. In case of discordance between status and command,
a signalling will outline it.
DIF.3004
Status of LCB circuit breaker.
YES
It is used to detect the actual status of the KM/MCB circuit
breaker. In case of discordance between status and command,
a signalling will outline it.
DIF.3011
Trip of GCB circuit breaker.
YES
Connect to this input the “tripped” contact of circuit breaker. If
the input is “active”, an alarm (block) with a fixed description
(language-dependant) is activated.
DIF.3012
Trip of ACB circuit breaker.
YES
Connect to this input the “tripped” contact of circuit breaker. If
the input is “active”, an alarm (block) with a fixed description
(language-dependant) is activated.
DIF.3013
Trip of BCB circuit breaker.
YES
Connect to this input the “tripped” contact of circuit breaker. If
the input is “active”, an alarm (block) with a fixed description
(language-dependant) is activated.
DIF.3014
Trip of LCB circuit breaker.
YES
Connect to this inp
ut the “tripped” contact of circuit breaker. If
the input is “active”, an alarm (block) with a fixed description
(language-dependant) is activated.