![Sices HS 315 Скачать руководство пользователя страница 124](http://html1.mh-extra.com/html/sices/hs-315/hs-315_technical-handbook_1263822124.webp)
106
Technical Handbook
4
16
0010
Circuit breakers status
5
32
0020
Circuit breakers commands
6
64
0040
Start/stop requests
7
128
0080
Fuel pump commands
8
256
0100
Charge procedure
Below you will find a table showing the codes of all possible events.
Code
Ver.
Recording cause
EVT.1001
01.00
Controller in OFF_RESET mode.
EVT.1002
01.00
Controller in MAN mode.
EVT.1003
01.00
Controller in AUTO mode.
EVT.1004
01.00
Controller in TEST mode.
EVT.1005
01.00
Controller in REMOTE START mode.
EVT.1010
01.00
Auxiliary source is missing.
EVT.1011
01.00
Auxiliary source is present (out of thresholds).
EVT.1012
01.00
Auxiliary source is present (in thresholds).
EVT.1013
01.00
Start inhibition activated (from digital input).
EVT.1014
01.00
Start inhibition deactivated (from digital input).
EVT.1020
01.00
Generator voltages are missing.
EVT.1021
01.00
Generator voltages are present (out of thresholds).
EVT.1022
01.00
Generator voltages are present (in thresholds).
EVT.1030
01.00
Closure command for GCB.
EVT.1031
01.00
Opening command for GCB.
EVT.1032
01.00
GCB closed.
EVT.1033
01.00
GCB opened.
EVT.1035
01.00
Closure command for ACB.
EVT.1036
01.00
Opening command for ACB.
EVT.1037
01.00
ACB closed.
EVT.1038
01.00
ACB opened.
EVT.1040
01.00
Engine stopped.
EVT.1041
01.00
Starting the engine.
EVT.1042
01.00
Engine running (rated speed).
EVT.1043
01.00
Cooling down cycle.
EVT.1044
01.00
Stopping the engine.
EVT.1045
01.00
Engine running (idle speed).
EVT.1050
01.00
Manual start command.
EVT.1051
01.00
Manual stop command.
EVT.1052
01.00
Automatic start command.
EVT.1053
01.00
Automatic stop command.
EVT.1054
01.00
Start command from digital input.
EVT.1055
01.00
Stop command from digital input.
EVT.1056
01.00
Start command from serial ports / USB / ETHERNET.
EVT.1057
01.00
Stop command from serial ports / USB / ETHERNET.
EVT.1058
01.00
Start command from real time clock.
EVT.1059
01.00
Stop command from real time clock.
EVT.1060
01.00
Start command from SMS.
EVT.1061
01.00
Stop command from SMS.
EVT.1062
01.00
Start command because loads are unsupplied.
EVT.1070
01.00
Fuel pump activated.
EVT.1071
01.00
Fuel pump deactivated.