Technical Handbook 31
Code
Description.
Note
DOF.0000 Not used.
DOF.0101 Used by PLC
Output used by the internal PLC logic
DOF.0102 Managed by serial ports.
The controller does not control the output with its own internal logics, but with the
controls it receives through the serial ports.
DOF.0103 AND/OR logics.
The status of the output is the result of the combination of the AND/OR logics. See
par. 0
DOF.1001 Preheating of glow plugs.
Command for glow plugs preheating for Diesel engines; see par. 9.7.6
DOF.1002 Enable for engine control unit.
Command for ECU enabling; see par. 9.7.6
DOF.1003 Fuel solenoid.
Command for the fuel interception solenoid; see par. 9.7.6
DOF.1004 Gas solenoid.
Command for activating the gas valve (for gas engines); see par. 9.7.6
DOF.1005 Command to start the engine.
Command for the starter motor; see par. 9.7.6
DOF.1006 Stop solenoid.
Command for engine stop with arrest when energized; see par.5.5.1.3 and par.
9.7.6
DOF.1007 Command for idle speed.
Some engines are provided with an output to reduce the rotational speed; see par.
9.7.6
DOF.1008 Selects battery 1.
Select battery 1 to start the engine; see par. 9.7.6
DOF.1009 Selects battery 2.
Select battery 2 to start the engine; see par. 9.7.6
DOF.1031 Coolant preheating.
Thermostat command for coolant pre-heating; see 9.7.6
DOF.1032 Fuel pump.
Fuel pump activation command.
DOF.1033 Command for pre-lubrication.
Command to activate the pre-lubrication pumps before starting the engine; see par.
9.7.6
DOF.1034 Solenoid for fuel pump.
Command to activate the fuel interception solenoid on the fuel pump line; see par.
9.7.6
DOF.1035 Inhibit DPF regeneration.
Command to inhibit the regeneration of the particulate filter; see par. 8.5.5.8.
DOF.1036 Force DPF regeneration.
Command to force the regeneration of the particulate filter; see par. 8.5.5.8.
DOF.2001 ACB (NC) under voltage coil.
See par. 9.8.1
DOF.2002 ACB opening coil.
See par. 9.8.1
DOF.2003 ACB closing coil.
See par. 9.8.1
DOF.2004 ACB stable opening command.
See par. 9.8.1
DOF.2031 GCB under voltage coil.
See par. 9.8.1
DOF.2032 GCB opening coil.
See par. 9.8.1
DOF.2033 GCB closing coil.
See par. 9.8.1
DOF.2034 GCB stable closing command
See par. 9.8.1
DOF.2041 BCB (NC) under voltage coil.
See par. 9.8.1
DOF.2042 BCB opening coil.
See par. 9.8.1
DOF.2043 BCB closing coil.
See par. 9.8.1
DOF.2044 BCB stable opening command.
See par. 9.8.1
DOF.2051 LCB (NC) under voltage coil.
See par. 9.8.1
DOF.2052 LCB opening coil.
See par. 9.8.1
DOF.2053 LCB closing coil.
See par. 9.8.1
DOF.2054 LCB stable opening command.
See par. 9.8.1
DOF.2261 Secondary LCB #1 command
See par. 9.4.3.
DOF.2262 Secondary LCB #2 command
See par. 9.4.3
DOF.2263 Secondary LCB #3 command
See par. 9.4.3
DOF.2264 Secondary LCB #4 command
See par. 9.4.3
DOF.2265 Secondary LCB #5 command
See par. 9.4.3
DOF.2266 Secondary LCB #6 command
See par. 9.4.3
DOF.2267 Secondary LCB #7 command
See par. 9.4.3
DOF.2268 Secondary LCB #8 command
See par. 9.4.3
DOF.3001 Off/reset.
It is activated when the controller is in OFF/RESET mode.
DOF.3002 Manual.
It is activated when the controller is in MAN mode.
DOF.3003 Automatic.
It is activated when the controller is in AUTO mode.
DOF.3004 Test.
It is activated when the controller is in TEST mode.
DOF.3005 Remote start.
It is activated when the controller is in REMOTE START mode.
DOF.3011 Not in Off/reset.
it is activated when the controller is
not
in OFF/RESET mode.
DOF.3012 One of the automatic modes.
It is activated when the controller is in one of the automatic operation modes, that
is AUTO, TEST or REMOTE START.
DOF.3032 Generator in tolerance.
It is active when the generator parameters are in the normal operation window
DOF.3033 Auxiliary source in tolerance.
It is
active when the auxiliary source parameters are within the “auxiliary source
presence” window
DOF.3061 Engine running.
Active after detection of the engine running status, even when it is started manually.
DOF.3062 Ready to supply.
The output will be act
ivated if the engine is in motion and if the “delay before
supplying” (P.0218) has been performed.
DOF.3151 Reset of the anomalies.
It is activated when the controller goes in RESET mode.
DOF.3152 External horn.
It is activated together with the internal siren.
DOF.3153 Lamp test.
It is activated with the controller in OFF/RESET mode by pressing the STOP
button.
DOF.3154 Acknowledge of the anomalies.
The controller activates this output for one second when the internal sequence of
faults acknowledgement is carried out.