Technical Handbook 185
Related parameters:
P.2001
Function of the input 01 or equivalent for the other inputs
P.2002
Delay for the input 01 or equivalent for the other inputs.
To disable:
P.2002 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the external over speed contact (feature DIF.4251 -
“Over speed”) (in parameter
P.2001 or equivalent for the other inputs) and if a time other than zero has been set for said
input (parameter P.2002 or equivalent). It is only enabled if the engine has been started by the
controller (if the command for the fuel solenoid is activated) and is disabled in the engine start
phase. Active if the configured input remains
continuously “active” for the configured time.
Type:
Alarm
Related parameters:
P.0110
Number of teeth of the pick-up wheel.
P.0111
Rpm/W ratio.
P.0133
Engine's nominal speed (primary).
P.0134
Engine's nominal speed (secondary).
P.0333
Maximum speed threshold (pick-up/w).
P.0334
Maximum speed delay (pick-up/w).
P.0700
Engine type.
To disable:
P.0334 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only if the controller acquires the measure of the engine speed; it
can acquire it through its pick-up input (JM_05, P.0110 other than zero) or through its W input
JM_07, P.0111 other than zero) or, finally, from CAN-BUS (P.0700 other than zero). It is only
enabled if the engine has been started by the controller (if the command for the fuel solenoid
is activated) and is disabled in the engine start phase. It is activated if the acquired speed
measure exceeds threshold P.0333 (percentage of the rated speed
– P.0133 or P.0134)
continuously, for time P.0334.
Type:
Alarm
Related parameters:
P.0105
Nominal frequency.
P.0331
Maximum speed threshold (frequency).
P.0332
Maximum speed delay (frequency).
To disable:
P.0332 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is only enabled if the AC voltages of the generator have been connected to JG
terminals. It is enabled if the engine has been started by the controller (if the command for the
fuel solenoid is activated) and is disabled in the engine start phases. It is activated if the
generator frequency exceeds threshold P.0331 (percentage of the rated frequency P.0105)
continuously for time P.0332.
Type:
Alarm
Category:
Generic
Related parameters:
P.0214 Duration of stopping cycle.