190
Technical Handbook
controller is configured to acquire such measure - function AIF.1110 or AIF.1111 in parameter
P.4009 or equivalent for the other inputs) and if a time other than zero has been set for the
protection (parameter P.0338). It is only enabled if the engine has been started by the
controller (if the command for the fuel solenoid is activated) and is disabled in the engine
start/stop phases. It is activated if the temperature remains continuously above or equal to
threshold P.0337 for time P.0338, but only after the time P.0216 (oil mask) from engine start
has elapsed (this is to allow you to start the engine idle, to cool it off).
Type:
Alarm
Related parameters:
P.4009
Function of the analogue input 2 (JQ) or equivalent for the other
inputs.
P.0216
Time mask for engine protections.
P.0375
Maximum oil temperature threshold.
P.0376
Maximum oil temperature delay.
P.0700
Engine type.
To disable:
P.0376 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
Engine.
This protection is enabled if the controller acquires the measurement of the oil temperature
(directly from the ECU of the engine or if one of the analogue inputs of the controller is
configured to acquire such measure - function AIF.1100 or AIF.1101 in parameter P.4009 or
equivalent for the other inputs) and if a time other than zero has been set for the protection
(parameter P.0376). It is only enabled if the engine has been started by the controller (if the
command for the fuel solenoid is activated) and is disabled in the engine start/stop phases. It
is activated if the oil temperature remains continuously above or equal to threshold P.0375 for
time P.0376, but only after the time P.0216 (oil mask) from engine start has elapsed (this is to
allow you to start the engine idle, to cool it off).
Type:
Warning
Related parameters:
P.0362
Low battery voltage threshold.
P.0363
Low battery voltage delay.
To disable:
P.0363 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
It is always enabled except when the cranking motor is activated. It is activated if the engine
battery voltage is continuously lower than the threshold P.0362 for time P.0363.
The threshold P.0362 is expressed as a percentage of the rated battery voltage which is not
configurable but is automatically selected by the controller between 12 e 24 Vdc. Selection is
made when the controller is powered and every time it is forced in OFF/RESET mode. If the
controller previously sensed a value lower than, or equal to, 17V, it considers to be powered
by a 12V battery, otherwise it will consider a 24 V rated voltage.
Type:
Warning
Related parameters:
P.0364
High battery voltage threshold.
P.0365
High battery voltage delay.
To disable:
P.0365 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-