HS315 has 12 digital inputs, which can be activated by connecting them to GND. When left
floating, the input brings itself to +Vbatt. Avoid situations where intermediate or undefined
voltage levels can occur.
Eight of the twelve inputs are located in the connector JN that is totally dedicated to these
inputs (see the picture). The remaining 4 inputs are in the connector JT, using 4 of the 8
available terminals.
The same command signal of an input can be shared by several different devices (for
instance one signal that goes to two HS315). In this case it is recommended to separate
the inputs with diodes, as shown in the figure below. This is to prevent the false
activation of the input when one of the devices is being turned off.
HS315
JN/T-x
HS315
JN/T-x