70
Technical Handbook
These parameters can be modified on the controller through the relative programming menu, with
the BoardPrg3xx and also through the web service in the appropriate configuration page of the
device. In details:
P.0530
parameter set to value “
1-YES
” enables the data issue towards “
Si.Mo.Ne
.”
server.
P.0531
parameter configures the IP address or the name of “
Si.Mo.Ne
” primary server,
while parameter
P.0533
the one of the secondary server. It is possible to set the IP
address in text format or the server name in full (i.e. “simone.sices.eu”) which will be
converted by the controller into IP address using the DNS server (suitably configured or
automatic on GPRS). It is possible to disable the connection towards the
primary/secondary server setting the empty string.
P.0532
parameter configures “
Si.Mo.Ne
” primary server port, while
P.0534
parameter
that of the secondary server. By setting the port address to zero the connection towards
the primary/secondary server is disabled. The default port is 53052 (check with SICES).
P.0535
parameter configures the interval of time to send periodic data towards the server
when the genset is running.
P.0536
parameter configures the interval of time to send periodic data towards the server
when the genset is off.
P.0537
parameter configures the interval of time in minutes to send the special packet
“Keep Alive Network”, used to indicate a minimum of activity to the server.
P.0539
parameter configures in which cases the device has to spontaneously send the
communication events to the server:
Bit
Value (hex) P.0539
Description
0
0001
For alarms and deactivations
1
0002
For warning
2
0004
For auxiliary source status
3
0008
For generator status
4
0010
For engine status
5
0020
For battery status
6
0040
For board operation mode
14
4000
For energy saving
16
8000
For diagnostic
P.0542
parameter allows to choose if to send to server the continuous voltage (DC) or
the phase to phase or phase to neutral alternate voltage (AC).
The parameters used and the status information for the communication with “Si.Mo.Ne” are
displayed on page S.21. In details:
Name
: identifies the plant name (which is supposed
to correspond to the one given on “
Si.Mo.Ne
” to
allow an easy identification of the device on
“
Si.Mo.Ne
” server web page.
Server
: identifies the IP address of the server to
which the data are sent. In case of connection on
GPRS network, the server name is displayed.
Status
: indicates the status, the date and the time of
the last connection (which is of the last data sent/received by the server) and the time left
before the next data issue. The status can be:
Status
Description
Stand-by
No connection
In process Connection to server in process
Ok
Connection to server correctly performed
Error
Connection to server failed
S.21 SIMONE |
Name: HS315x_001
Serv: 192.168.1.140
Status: ok
15/09 12.10.55