Technical Handbook
DIF.4033
Deactivation (when FUEL is active).
YES
YES
If the input is active and the output command for the fuel
solenoid is also active (JL_03), a deactivation is issued: the
message shown is the one set by means of the related
parameters.
DIF.4034
Alarm (when FUEL is active).
YES
YES
If the input is active and the output command for the fuel
solenoid is active (JL_03), an alarm (block) is issued. The
message
shown is the one set by means the related “text”
parameter.
DIF.4041
Warning (when GAS is active).
YES
YES
If the input is “active” and the command of an output set as
DOF.1004
– “Gas valve” is also active, a warning is issued: the
message shown is the one set by means of the related
parameters.
DIF.4042
Warning latched (when GAS is active).
YES
YES
If the input is “active” and the command of an output set as
DOF.1004
– “Gas valve” is also active, a latched warning is
issued (it requires an explicit reset): the message shown is the
one set by means of the related parameters.
DIF.4043
Deactivation (when GAS is active).
YES
YES
If the input is
“active” and the command of an output set as
DOF.1004
– “Gas valve” is also active, a deactivation is issued:
the message shown is the one set by means of the related
parameters.
DIF.4044
Alarm (when GAS is active).
YES
YES
If the input is “active” and the command of an output set as
DOF.1004
– “Gas valve” is also active, an alarm (block) is
issued: the message shown is the one set by means of the
related parameters.
DIF.4051
Warning (stops fuel pump).
YES
YES
If the input is active, a warning is issued: the message shown
is the one set by means
the related “text” parameter. The
controller blocks the fuel pump if
this input is “active”
DIF.4052
Warning latched (stops fuel pump).
YES
YES
If the input is active, a latched warning is issued (it requires an
explicit reset): the message shown is the one set by means the
related “text” parameter. The controller blocks the fuel pump if
this input is “active”
DIF.4053
Deactivation (stops fuel pump).
YES
YES
If the input is active, a deactivation is issued: the message
shown is the one set by means the re
lated “text” parameter.
The controller blocks the fuel pump if
this input is “active”
DIF.4054
Alarm (stops fuel pump).
YES
YES
If the input is active, an alarm (block) is issued: the message
shown is the one set by means the related “text” parameter.
The controller blocks the fuel pump if
this input is “active”
DIF.4062
Warning latched (subject to override).
YES
YES
If the input is “active”, normally latched warning is issued (it
requires an explicit reset). If the “override engine protections”
function is enabled, a warning is issued. The message shown
is the one set by means of the related parameters.
DIF.4063
Deactivation (subject to override).
YES
YES
If the input is “active”, normally a deactivation is activated. If
the “override engine protections” function is enabled, a warning
is issued. The message shown is the one set by means of the
related parameters.
DIF.4064
Alarm (subject to override).
YES
YES
If the input is “active”, normally an alarm (block) is activated. If
the “override engine protections” function is enabled, a warning
is issued. The message shown is the one set by means of the
related parameters.
DIF.4211
Minimum fuel level
YES
If the input is “active”, an alarm (block) with a fixed description
(language-dependant) is activated. This function can be also
used for the “Fuel pump management” (see par. 9.7.13).
DIF.4212
Low fuel level
YES
If the input is “active”, a warning with a fixed description
(language-dependant) is activated. This function can be also
used for the “Fuel pump management” (see par. 9.7.13).
DIF.4213
High fuel level
YES
If the input is “active”, a warning with a fixed description
(language-dependant) is activated. This function can be also
used for the
“Fuel pump management” (see par. 9.7.13).
DIF.4221
Minimum oil pressure
YES
When the input is “active”, if the time set by means of the
P.0216 parameter from engine start has elapsed, a fixed
description (language-dependant) alarm (block) is activated.
DIF.4222
Low oil pressure
YES
When the input is “active”, if the time set by means of the
P.0216 parameter from engine start has elapsed, a fixed
description (language-dependant) warning is activated.
DIF.4231
High coolant temperature
YES
When the input is “active”, if the time set by means of the
P.0216 parameter from engine start has elapsed, a fixed
description (language-dependant) warning is activated.
DIF.4232
Maximum coolant temperature
YES
When the input is “active”, if the time set by means of the
P.0216 parameter from engine start has elapsed, a fixed
description (language-dependant) warning is activated.
DIF.4251
Over speed
YES
If the input is “active”, an alarm (block) with a fixed description
(language-dependant) is activated.