Technical Handbook 33
144: Low oil pressure (from CANBUS).
158: High oil temperature (from CANBUS).
159: Maximum oil temperature (from CANBUS).
198: Warnings - Yellow lamp (from CANBUS).
199: Alarms - Red lamp (from CANBUS).
DOF.4033 Anomalies of speed regulator.
It is activated in case of faults in the engine rotational speed, i.e.:
003: Minimum generator's frequency.
004: Maximum generator's frequency.
017: Maximum speed (from digital input).
018: Maximum speed (from measure).
019: Maximum speed (from Hz).
058: Low generator's frequency.
060: High generator's voltage.
118: Maximum speed (from CANBUS).
DOF.4034 Anomalies of the fuel.
It is activated in case of faults in the fuel level, i.e.:
025: Minimum fuel level (from contact).
026: Minimum fuel level (from measure).
027: Low fuel level (from contact).
028: Low fuel level (from measure).
029: High fuel level (from contact).
030: High fuel level (from measure).
160: Water in fuel (from CANBUS).
DOF.4035 Anomalies of circuit breakers.
It is activated in case of faults of the GCB and MCB breakers, i.e.:
013: ACB not closed.
014: GCB not closed.
023: ACB not opened.
024: GCB not opened.
113: BCB not closed.
114: LCB not closed.
123: BCB not opened.
124: LCB not opened.