198
Technical Handbook
Related parameters:
P.2001
Function of the input 01 or equivalent for the other inputs
P.2002
Delay for the input 01 or equivalent for the other inputs.
To disable:
P.2002 = 0
Enabled in:
MAN,
AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the BCB status (function DIF.3006 -
“Status of BCB circuit breaker”) (in parameter
P.2001 or equivalent for the other inputs) and if a time other than zero has been set for said
input (parameter P.2002 or equivalent). It activates only when BCB is commanded to open
and the status acquired is continuously “closed” for the time set.
Type:
Warning
Related parameters:
P.2001
Function of the input 01 or equivalent for the other inputs
P.2002
Delay for the input 01 or equivalent for the other inputs.
To disable:
P.2002 = 0
Enabled in:
MAN,
AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the LCB status (function DIF.3007 -
“Status of LCB circuit breaker”) (in parameter
P.2001 or equivalent for the other inputs) and if a time other than zero has been set for said
input (parameter P.2002 or equivalent). It activates only when LCB is commanded to open
and the status acquired is co
ntinuously “closed” for the time set.
Type:
Warning
Related parameters:
P.0700
Engine type.
P.0704
Can-Bus alarms disable mask.
To disable:
bit 4 of P.0704 on
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only if the board is connected to the engine via the CAN BUS
(P.0700 different from zero). It is activated when the engine signals the coolant high
temperature state over the CAN BUS. Only for SCANIA engines, the protection is activated
only after the time P.0216 (oil mask) from engine start has elapsed.
Type:
Alarm
Related parameters:
P.0700
Engine type.
P.0704
Can-Bus alarms disable mask.
To disable:
bit 5 of P.704 on
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
Engine.
This protection is enabled only if the board is connected to the engine via the CAN BUS
(P.0700 different from zero). It is activated when the engine signals the coolant maximum
temperature state over the CAN BUS.
Only for SCANIA engines, the protection is activated
only after the time P.0216 (oil mask) from engine start has elapsed.