Technical Handbook 81
No parameter modification is allowed.
When entering “uuu” in “P.0000-Access code”,
the operator is identified as “End User” and can to modify all parameters associated
to the end user. By entering “iii”, the operator is identified as "installer” but, as no
password is associated to the manufacturer, the controller identifies him/her as
"manufacturer”. After entering code all parameters are modifiable.
Example 4
:
P.0001
=”ccc”
P.0002
=”iii”
P.0003
=”uuu”
No paramete
r modification is allowed. When entering “uuu” in “P.0000-Access code”,
the operat
or is identified as “End User” and can modify all parameters associated to
the end user. By entering “iii”, the operator is identified as "installer” and can modify
all param
eters associated to “installer” and “end user”. When entering “ccc”, the
operator
is identified as "manufacturer” and is therefore allowed to modify any
parameter of the controller board.
Example 5
:
P.0001
=”ccc”
P.0002=0
P.0003=0
As no password is associated to End User and Installer, programming the relevant
parameters is allowed with
out entering anything in “P.0000-Access code”. To modify
the parameters associated to Manufacturer, simply enter “ccc” in “P.0000-Access
code”.
Example 6
:
P.0001=0
P.0002
=”iii”
P.0003=0
As no password is associated to the End User, programming the relevant parameters
is allowed without entering anything in “P.0000-Access code”. When entering “iii” in
“P.0000-Access code” the operator is identified as “installer” but, as no password is
associated to “manufacturer”, the controller identifies him/her as "manufacturer”. After
entering code all parameters are modifiable.
Example 7
:
P.0001=
”ccc”
P.0002
=”iii”
P.0003=0
As no password is associated to End User, programming the relevant parameters is
allowed without entering anything in “P.0000”. By entering “iii”, the operator is identified
as "insta
ller” and can modify all parameters associated to “installer” and “end user”.
When entering “ccc” in P.0000, the operator is identified as “manufacturer” and can
modify all parameters.
Example 8
:
P.0001
=”ccc”
P.0002=000
P.0003
=”uuu”
No parameter modification is allowed. When entering the “uuu” code in “P.0000-
Access code”, the operator is identified as “End User” but, as no password is
asso
ciated to “Installer” and “Manufacturer”, the controller acknowledges him/her as
"
installer”. Therefore, he/she can modify all controller parameters associated to
installer and end user. When entering “ccc” in “P.0000 - Access code”, the operator is
identi
fied as “manufacturer” and can modify all parameters.
A parameter value can always be read but it can only be modified in case the "P.0000
” contains
a proper password. Parameters P.0001, P.0002 and P.0003 are excluded: they are not
displayed in case "P.0000-
Access code” does not contain a proper password.
Parameter P.0469
– “Serial ports password” can only be viewed and/or modified through
operator panel and with at least Installer rights.
When accessing programming and setting the password ("P.0000
”), parameters P.0001,
P.0002 and P.0003 might not be immediately displayed. To enable display, return to the
previous menu and then re-enter.
In case the code set as password is forgotten, access can only be recovered if you know the
higher-level password. Otherwise (or in the event the manufacturer password is lost) you need
to send the controller board back to the factory to have its associated programming functions
unlocked.
This is the reason why we recommend setting
at least the “Manufacturer” password (P.0001):
in case someone else sets up this password, or a lower level one (even unwillingly) without