Technical Handbook 191
It is always enabled except when the cranking motor is activated. It is activated if the battery
voltage is continuously above threshold P.0364 for time P.0365.
The threshold P.0364 is expressed as a percentage of the rated battery voltage which is not
configurable but is automatically selected by the controller between 12 e 24 Vdc. Selection is
made when the controller is powered and every time it is forced in OFF/RESET mode. If the
controller previously sensed a value lower than, or equal to, 17V, it considers to be powered
by a 12V battery, otherwise it will consider a 24 V rated voltage.
Type:
Configurable
Related parameters:
P.0424
Maintenance interval 1 (running hours).
P.0425
Kind of action for maintenance 1.
To disable:
P.0424 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
Engine.
It is activated after P.0424 engine running hours since parameter P.0424 was last set, by
issuing an anomaly whose type is configurable by means parameter P.0425. It cannot be
cancelled even disconnecting the controller's power supply. It can be cancelled only by setting
P.0424 again, setting it to zero to disable the function or confirming the actual value or setting
a new one.
Engine operating hours are counted even when engine is not started by the controller.
To be programmed, parameters P.0424 and P.0425
require “installer” access level: this
function can be used for gen-set rental to lock the gen-set when the established hours are
elapsed.
Type:
Configurable
Related parameters:
P.0436
Maintenance interval 2 (running hours).
P.0437
Kind of action for maintenance 2.
To disable:
P.0436 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
Engine.
It is activated after P.0436 engine running hours since parameter P.0436 was last set, by
issuing an anomaly whose type is configurable by means parameter P.0437. It cannot be
cancelled even disconnecting the controller's power supply. It can be cancelled only by setting
P.0436 again, setting it to zero to disable the function or confirming the actual value or setting
a new one.
Engine operating hours are counted even when engine is not started by the controller.
To be programmed, parameters P.0436 and P.0437
require “installer” access level: this
function can be used for gen-set rental to lock the gen-set when the established hours are
elapsed.
Type:
Alarm
Related parameters:
P.2001
Function of the input 01 or equivalent for the other inputs.
P.2002
Delay for the input 01 or equivalent for the other inputs.
P.0216
Time mask for engine protections.
To disable:
P.2002 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START