30
Technical Handbook
•
A zero-bit means that the output is normally on standby and starts operating when the
related feature requires it.
•
A one-bit means that the output is normally operating and goes on standby when the
related function requires it.
•
The logical status of the digital outputs is displayed on page S.13 (0 = output inactive, 1 =
output active).
The mapping of the outputs on the controller is:
BIT Value Hexadecimal Output
0
1
0001
Output 1
1
2
0002
Output 2
2
4
0004
Output 3
3
8
0008
Output 4
4
16
0010
Output 5 (JL-1)
5
32
0020
Output 6 (JL-3)
6
64
0040
Output 7 (JI-4)
7
128
0080
Output 8 (JI-1)
8
256
0100
Output 9
9
512
0200
Output 10
10
1024
0400
Output 11
11
2048
0800
Output 12
While the mapping of the outputs on the two DITEL 8 OUT modules is:
BIT Value
Hexadecimal Output
0
1
0001
Output 1
1
2
0002
Output 2
2
4
0004
Output 3
3
8
0008
Output 4
4
16
0010
Output 5
5
32
0020
Output 6
6
64
0040
Output 7
7
128
0080
Output 8
8
256
0100
Output 9
9
512
0200
Output 10
10
1024
0400
Output 11
11
2048
0800
Output 12
12
4096
1000
Output 13
13
8192
2000
Output 14
14
16384 4000
Output 15
15
32768 8000
Output 16
Basically, if you want to reverse the logic of an output you need to add the corresponding value
into its parameter.
for example, if you want to invert outputs 3 and 4 on the controller you must set P.3000 =12
(0x000C) (i.e. 4+8); if you want to invert outputs 5 and 10 of the second DITEL gen-set (16 IN
+ 16 OUT) you must set P.3250=1056 (0x0420) (i.e. 32+1024)
As default, all the bits are set to 0.
The digital outputs can be used directly as command for devices outside the controller, or for
reporting certain operating conditions.
See below the outputs configurable on the digital outputs: