Technical Handbook 213
•
DIF.4013
– “General deactivation (after oil delay)”.
•
DIF.4014
– “General alarm (block) (after oil delay)”.
If the input stays continuously "active" for the time configured, and if the time set by
means of the P.0216 parameter (Engine protections mask time) has elapsed, an
anomaly of the related type is activated: the message shown is the one set by means
of the related parameters.
Remark: if engine’s protections override function is enabled,
this anomaly becomes a warning.
•
DIF.4021
– “General warning (if GCB is closed)”.
•
DIF.4022
– “General latched warning (if GCB is closed)”.
•
DIF.4023
– “General deactivation (if GCB is closed)”.
•
DIF.4024
– “General alarm (block) (if GCB is closed)”.
If the input stays continuously "active" for the time configured, with GCB closed, an
anomaly of the related type is activated: the message shown is the one set by means
of the related parameters.
•
DIF.4031
– “General warning (if FUEL is activated)”.
•
DIF.4032
– “General latched warning (if FUEL is activated)”.
•
DIF.4033
– “General deactivation (if FUEL is activated)”.
•
DIF.4034
– “General alarm (block) (if FUEL is activated)”.
If the input stays continuously "active" for the time configured and if the command for
the fuel solenoid is active, an anomaly of the related type is activated: the message
shown is the one set by means the related parameters.
•
DIF.4041
– “General warning (if GAS is activated)”.
•
DIF.4042
– “General latched warning (if GAS is activated)”.
•
DIF.4043
– “General deactivation (if GAS is activated)”.
•
DIF.4044
– “General alarm (block) (if GAS is activated)”.
If the input stays continuously "active" for the time configured and if the command for
the gas valve (for gas driven engines) is active, an anomaly of the related type is
activated: the message shown is the one set by means the related parameters.
•
DIF.4051
– “General warning (if fuel pump is activated)”.
•
DIF.4052
– “General latched warning (if fuel pump is activated)”.
•
DIF.4053
– “General deactivation (if fuel pump is activated)”.
•
DIF.4054
– “General alarm (block) (if fuel pump is activated)”.
If the input stays continuously "active" for the time configured, an anomaly of the
related type is activated: the message shown is the one set by means of the related
parameters. The controller locks the fuel pump if
this input is “active” (The pump is
stopped and not set to “MAN-OFF”).
•
DIF.4062
– “General latched warning (subject to override)”.
•
DIF.4063
– “General deactivation (subject to override)”.
•
DIF.4064
– “General alarm (block) (subject to override)”.
If the input stays continuously "active" for the time configured, an anomaly of the
related type is activated: the message shown is the one set by means of the related