Technical Handbook 23
DIF.3101
External sensor for auxiliary source.
When the input is “active” the auxiliary source is considered to
be “in tolerance”
DIF.3201
Generic status (page 1).
YES
If the related input is active, the controller will show the text
defined by the related text parameter on page S.07 of the
display.
DIF.3202
Important status (page 1).
YES
If this input is
“active”, the controller displays the text set in the
related parameters associated to the input on page S.07, which
is displayed immediately
DIF.3203
Generic status (page 2).
YES
If the related input is active, the controller will show the text
defined by the related text parameter on page S.08 of the
display.
DIF.3204
Important status (page 2).
YES
If this input is “active”, the controller displays the text set in the
related parameters associated to the input on page S.08, which
is displayed immediately
DIF.3205
Generic status (page 3).
YES
If the related input is active, the controller will show the text
defined by the related text parameter on page S.09 of the
display.
DIF.3206
Important status (page 3).
YES
If this input is “active”, the controller displays the text set in the
related parameters associated to the input on page S.09, which
is displayed immediately
DIF.3301
Level for starting fuel pump.
If the input is “active” the fuel pump is started (see par.9.7.13).
DIF.3302
Level for stopping fuel pump.
If the input is “active” the fuel pump is stopped (see par. 9.7.13)
DIF.4001
Generic warning.
YES
YES
If the input is “active”, a warning is issued: the message shown
is the one
set by means the related “text” parameter.
DIF.4002
Generic warning latched.
YES
YES
If the input is “active”, a latched warning is issued (it requires
an explicit reset): the message shown is the one set by means
the related “text” parameter.
DIF.4003
Generic deactivation.
YES
YES
If the input is
“active”, a deactivation command is issued: the
message shown is the one set by means of the related
parameters.
DIF.4004
Generic alarm.
YES
YES
If the input is “active”, an alarm (block) is issued: the message
shown is the one set by mea
ns the related “text” parameter.
DIF.4011
Warning (after oil delay).
YES
YES
If the input is active, a warning is issued if the time set by
means P.0216 is elapsed from the engine running detection.
The message shown is the one
set by means the related “text”
parameter.
DIF.4012
Warning latched (after oil delay).
YES
YES
If the input is active, a latched warning is issued (it requires an
explicit reset) if the time set by means P.0216 is elapsed from
the engine running detection. The message shown is the one
set by means the related “text” parameter.
DIF.4013
Deactivation (after oil delay).
YES
YES
When the input is “active”, if the time set by means of the
P.0216 parameter from engine start has elapsed, a
deactivation command is issued: the message shown is the
one set by means of the related parameters. If the DIF.2062
–
“Override engine protections”, or the DIF.2063 - “Complete
Protections Override” functions are active, a warning is issued
instead of a deactivation. See par. 11.1 and 11.1.2
DIF.4014
Alarm (after oil delay).
YES
YES
If the input is active, an alarm (block) is issued if the time set
by means P.0216 is elapsed from the engine running detection.
The message shown is the one set by means the related “text”
parameter. If the DIF.2062
– “Override engine protections”, or
the DIF.2063 -
“Complete Protections Override” functions are
active, a warning is issued instead of an alarm (block). See par.
11.1 and 11.1.2
DIF.4021
Warning (when GCB is closed).
YES
YES
If the input is "active" and the GCB is closed, a warning is
issued. The message shown is the one set by means the
related text parameter.
DIF.4022
Warning latched (when GCB is closed). YES
YES
If the input is "active" and the GCB is closed, a latched warning
is issued (it requires an explicit reset). The message shown is
the one set by means the related text parameter.
DIF.4023
Deactivation (when GCB is closed).
YES
YES
If the input is "active" and the GCB is closed, a deactivation
command is issued: the message shown is the one set by
means of the related parameters.
DIF.4024
Alarm (when GCB is closed).
YES
YES
If the input is "active" and the GCB is closed, an alarm (block)
is activated. The message shown is the one set by means of
the related parameters.
DIF.4031
Warning (when FUEL is active).
YES
YES
If the input is active and the output command for the fuel
solenoid is active (JL_03), a warning is issued. The message
shown is the one set by means the related “text” parameter.
DIF.4032
Warning latched (when FUEL is active). YES
YES
If the input is active and the output command for the fuel
solenoid is active (JL_03), a latched warning is issued (it
requires an explicit reset). The message shown is the one set
by means the related “text” parameter.