P.0214 parameter ("Duration of the stopping cycle"): if at the end of this phase the engine has
not stopped, A021 shutdown is activated - "Failure to stop".
Note: normally the stopping cycle lasts P.0214 seconds even if the engine stops in a shorter
time. If during the stopping cycle a new automatic intervention of the generator is required, the
same stopping cycle will be arrested only when the engine is completely stopped. In this case
HS315 ensures that the STOP and FUEL controls do not overlap.
HS315 provides a parameter that allows configuring a delay (from the moment when the
"started engine" condition is recognized) within which the oil pressure protections are disabled.
This is to allow time for the pump to pressurize oil and prevent false alarms. The delay is
configurable with P.0216 parameter ("Engine protection masking time").
The controller records the following events if the status of the engine varies (if enabled by the
bit 3 of P.0441 parameter):
•
EVT.1040: engine stopped.
•
EVT.1041: starting the engine.
•
EVT.1042: engine running (rated speed).
•
EVT.1043: cooling down cycle.
•
EVT.1044: stopping the engine.
•
EVT.1045: engine running (idle speed).
Moreover, the controller records the following events at the changing of start/stop requests (if
enabled by the bit 6 of P.0441 parameter):
•
EVT.1050: Manual start command.
•
EVT.1050: Manual stop command.
•
EVT.1052: Automatic start command.
•
EVT.1053: Automatic stop command.
•
EVT.1054: Start command from digital input.
•
EVT.1055: Stop command from digital input.
•
EVT.1056: Start command from serial ports / USB / ETHERNET.
•
EVT.1057: Stop command from serial ports / USB / ETHERNET.
•
EVT.1058: Start command from real time clock.
•
EVT.1059: Stop command from real time clock.
•
EVT.1060: Start command from SMS.
•
EVT.1061: Stop command from SMS.
•
EVT.1062: Start command because loads are unsupplied.
The following functions for the configuration of the digital inputs are linked to engine
management (besides those described for engine direct controls):
•
DOF.3061: the output will be activated if the engine is in motion.