Technical Handbook 233
•
Cell Voltage Difference Alarm
•
Module Temp Difference Alarm
•
Temp Out of Limit Fault
•
Current Out of Limit Fault
•
Cell Over Voltage Fault
•
Cell Under Voltage Fault
•
Over Charging Current Fault
•
Over Discharging Current Fault
•
Over Temperature Fault
•
Under Temperature Fault
•
Cell Voltage Difference Fault
•
Module Temp Difference Fault
•
SPI Comm Fault
•
Voltage Sensing Line Open
•
Ref Voltage Out of Range
•
CFET Short Fault
•
DFET Short Fault
•
MCU Fault
See [8].
It is a battery provided with an internally BMS system that regulates the charge. Its serial port
is normally configured with the Modbus/RTU protocol. To use it with HS315, set it as
Modbus/RTU, 115200 baud, 8 bits, no parity, 2 stop bits. The Modbus address pre-assigned
to the battery is "1".
HS315 acquires the following data from the battery:
Data
UM
Page
Battery voltage
Vdc
M.15
Charge/discharge current
Adc
M.15
Average temperature
°C
M.15
Charge level
Ah
M.15
SOH project
%
*
SOC min.
%
*
Nominal/extended IMD
Adc
*
Nominal/extended IMR
Adc
*
Factorized IMR
Adc
*
Battery mode
-
*
Charge mode
-
*
Minor Error
-
*
Major Error
-
*
Anomalies
-
S.02
*: these data are not displayed; they are readable by HS315 via Modbus.