Technical Handbook 161
o
042 - Minimum oil pressure (from measure).
o
142 - Minimum oil pressure (from CANBUS).
o
054 - High oil temperature (from measure).
o
158 - High oil temperature (from CANBUS).
o
035 - Maximum oil temperature (from measure).
o
159 - Maximum oil temperature (from CANBUS).
o
037 - Low battery voltage (from measure).
o
137 - Low battery voltage (from CANBUS).
o
038 - High battery voltage (from measure).
o
198 - Warnings - Yellow lamp (from CANBUS).
o
199 - Alarms - Red lamp (from CANBUS).
o
062 - CANBUS 0 (engine): BUS-OFF.
o
098 - CANBUS 0 (engine): timeout without data.
o
039 - Service required (1st counter).
o
040 - Service required (2nd counter).
o
050 - Service required (counter of days).
o
049 - Maximum power.
•
DOF.4033: the controller activates this output to signal the presence of at least one
anomaly related to the engine speed.
o
017 - Maximum speed (from digital input).
o
018 - Maximum speed (from measure).
o
019 - Maximum speed (from Hz).
o
118 - Maximum speed (from CANBUS)
o
003 - Minimum generator's frequency.
o
058 - Low generator's frequency.
o
060 - High generator's frequency.
o
004 - Maximum generator's frequency.
•
DOF.4034: the controller activates this output to signal the presence of at least one
anomaly related to the engine fuel.
o
025 - Minimum fuel level (from contact).
o
036 - Minimum fuel level (from measure).
o
027 - Low fuel level (from contact).
o
028 - Low fuel level (from measure).
o
029 - High fuel level (from contact).
o
030 - High fuel level (from measure).
o
160 - Water in fuel (from CANBUS).