Technical Handbook 183
To disable:
Bit 0 of P.0495=1
Enabled in:
AUTO, TEST, REMOTE START
Override:
-
This protection is always enabled if the stop command comes through the communication
ports or via SMS; it can be disabled for the STOP button by setting the bit 0 of parameter
P.0495 to 1.
It is activated when pressing the STOP button on the front panel or sending a stop command
through the communication port or via SMS, while in AUTO, TEST or REMOTE START mode.
Type:
Alarm
Related parameters:
P.0217
Maximum time for operating conditions.
To disable:
P.0217=0
Enabled in:
AUTO, TEST, REMOTE START
Override:
Generator,
Full.
This protection is only enabled if the engine has been started by the controller (if the command
for the fuel solenoid is activated) and it is disabled during the crank/stop cycles. It is activated
when the generator voltages (DC or AC) and the generator frequency (or the engine speed)
are not steady within tolerance range within time P.0217 from the engine running
acknowledgement (or from the end of the engine’s idle cycle, if enabled).
Type:
Configurable
Related parameters:
P.9502
Nominal current of the generator.
P.9695
Generator reverse current threshold.
P.9696
Generator reverse current delay.
P.9697
Generator reverse current action.
To disable:
P.9696 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
Generator,
Full.
This protection is only enabled if the engine has been started by the controller (if the command
for the fuel solenoid is activated) and it is disabled during the crank/stop cycles. It is activated
if, in the previous conditions, the generator current is negative and has an absolute value
continuously above threshold P.9695 (percentage of the nominal current P.9502), for time
P.9696. Type is configurable with parameter P.9697 (though it cannot be configured as
warning).
Type:
Warning / latched warning
Related parameters:
P.2001
Function of the input 01 or equivalent for the other inputs
P.2002
Delay for the input 01 or equivalent for the other inputs.
To disable:
P.2002 = 0
Enabled in:
MAN,
AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only when one of the digital inputs of the controller is configured to
acquire the ACB status (function DIF.3002 -
“Status of ACB circuit breaker”) (in parameter
P.2001 or equivalent for the other inputs) and if a time other than zero has been set for said
input (parameter P.2002 or equivalent). It activates only when ACB is commanded to close
and the status acquired is continuously “open” for the time set. In MAN it is a warning, in the
other modes it becomes a latched warning.