110
Technical Handbook
The fast analogues are recorded at a pace configurable by means of the parameter P.0442
(interval in seconds) and the default interval is 60 seconds. This archive provides a total
storage capability of 42 records. Every following record overwrites the older one. The controller
records the analogue values described in par. 8.5.6.4.
The slow analogues are recorded at a pace configurable by means of the parameter P.0443
(interval in minutes) and the default interval is 30 minutes. This archive provides a total storage
capability of 64 records. Every following record overwrites the older one. The controller records
the analogue values described in par. 8.5.6.4.
The controller performs a series of recordings of maximum peaks for some significant
measures:
•
Total active power: the maximum peak is recorded, having the date/time and the
measure of the engine coolant temperature (if available) associated.
•
Coolant temperature: the maximum peak is being recorded, with date/time associated.
To display all records, the controller uses one page of the display.
Use the ▲ and ▼ buttons
to scroll cyclically trough all recordings.
The second line shows the record currently displayed, out of the total number of records (the
total number of records is 2).
The fourth line shows a description of the peak recording currently displayed:
•
Maximum power
•
Maximum coolant temperature
The sixth line shows the recording date and time. The seventh line displays the recorded
measure (power, temperature etc.) A second measure recorded together with the main
measure can be displayed on the eighth line:
•
The power is recorded together with the coolant temperature.
If certain data are not available at the time of recording, dashes will be displayed.
The controller records only the DTCs that the engine control unit (ECU interface) sends over
the CAN-BUS line.
Basically, depending on the installed engine, the diagnostic message consists of the DTC,
SPN and fault description. This archive can store up to 16 records. Every following record
overwrites the older one.
To display all records, the controller uses one page of the display.
H.33 HISTORY LOGS |
5 PEAKS 1/02
-----------------------
Maximum power
17/03/2014 10:35:54
345.4 kW
( 88 °C)
Содержание HS 315
Страница 1: ...File name EAAM058607EN docx Rev 07 Date 25 09 2019 ID Document EAAM0586 Product HS315...
Страница 17: ...Technical Handbook xvii...
Страница 18: ......
Страница 23: ...Technical Handbook 5 Rear view Hall...
Страница 254: ......