212
Technical Handbook
•
JH4 can be used for auxiliary source neutral only (warning).
The controller is
configured to acquire at least one AC voltage of the auxiliary source: in this case, the
terminal JH-4 can be used only to acquire the neutral (otherwise leave P.9618
= “000
– Not used”).
•
Capacity of battery not set (block).
The parameter P.9642 is set to zero: set it with
the rated battery capacity.
•
Discharge current not set (block).
The parameter P.9643 is set to zero: set it with
the rated discharge current.
Type:
Configurable
Related parameters:
P.4009
Function analogue input 2 (JQ) or equivalent for the other inputs
P.4010
Message analogue input 2 (JQ) or equivalent for the other
inputs
P.4011
Threshold 1 analogue input 2 (JQ) or equivalent for the other
inputs
P.4012
Delay 1 analogue input 2 (JQ) or equivalent for the other inputs
P.4013
Configuration 1 analogue input 2 (JQ) or equivalent
P.4014
Threshold 2 analogue input 2 (JQ) or equivalent for the other
inputs
P.4015
Delay 2 analogue input 2 (JQ) or equivalent for the other inputs
P.4016
Configuration 2 analogue input 2 (JQ) or equivalent
To disable:
P.4012
or
P.4015
= 0 (for input 2 (JQ) or equivalent for other inputs.
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
Configurable
These anomalies are triggered by the analogue
measure’s thresholds. See [1] to check the
correspondence between alarm code and analogue input.
See par. 5.6.5 for configuring the activation thresholds for these anomalies.
Type:
Warning
Related parameters:
P.2001
Feature of the input 01 or equivalent for the other inputs
P.2002
Delay for the input 01 or equivalent for the other inputs
P.2003
Message for the input 01 or equivalent for the other inputs
To disable:
P.2002
= 0 (for input 01 or equivalent for other inputs).
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
Configurable
These anomalies are triggered by the digital inputs configured with the following functions:
•
DIF.4001
– “Generic warning”.
•
DIF.4002
– “Generic latched warning”.
•
DIF.4003
– “Generic deactivation”.
•
DIF.4004
– “Generic alarm (block)”.
If the input stays continuously "active" for the time configured, an anomaly of the
related type is activated: the message shown is the one set by means of the related
parameters.
•
DIF.4011
– “General warning (after oil delay)”.
•
DIF.4012
– “General latched warning (after oil delay)”.