204
Technical Handbook
Type:
Warning
Related parameters:
P.9641
Nominal voltage (DC).
P.9711
Battery voltage hysteresis.
P.9716
High battery voltage threshold.
P.9717
High battery voltage delay.
To disable:
P.9717 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is activated if the measure of the plant battery voltage remains continuously
above to threshold P.9716 (percentage of the rated voltage P.9641) for time P.9717.
Type:
Latched warning
Related parameters:
P.9641
Nominal voltage (DC).
P.9711
Battery voltage hysteresis.
P.9718
Max battery voltage threshold.
P.9719
Max battery voltage delay.
To disable:
P.9719 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is activated if the measure of the plant battery voltage remains continuously
above to threshold P.9718 (percentage of the rated voltage P.9641) for time P.9719.
Type:
Warning
Related parameters:
P.9721
Battery current hysteresis.
P.9722
High battery current threshold.
P.9723
High battery current delay.
To disable:
P.9723 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is activated if the measure of the plant battery current remains continuously
above to threshold P.9722 for time P.9723.
Type:
Latched warning
Related parameters:
P.9724
High battery current threshold.
P.9725
High battery current delay.
To disable:
P.9725 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
HS315 performs a time-dependent current protection (therefore, the higher the current
overload, the shorter the reaction time) The curve used is called EXTREMELY INVERSE with
function I
2
t. See description for anomaly 006.