Technical Handbook 197
To disable:
P.0354 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled if the controller acquires the measurement of the coolant
temperature (directly from the ECU of the engine or if one of the analogue inputs of the
controller is configured to acquire such measure - function AIF.1110 or AIF.1111 in parameter
P.4009 or equivalent for the other inputs) and if a time other than zero has been set for the
protection (parameter P.0354). It is activated if the temperature remains continuously above
or equal to threshold P.0353 for time P.0354.
Type:
Configurable
Related parameters:
P.0700
Engine type.
P.0709
Action on Can-Bus fault.
P.0711
Maximum time without messages from engine.
To disable:
P.0711 = 0 (not for MTU engines)
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
Engine.
It’s enabled only if CAN-BUS is configured (P.0700 other than zero). For MTU MDEC engines
(value from 140 to 147 in parameter P.0700), it is enabled as per specification when the
controller does not continuously receive the message NMT ALIVE PDU for the set time. For
the other types of engines, it is activated if the controller does not continuously receive
messages from the engine for time P.0711. P.0709 configures the kind of protection.
Type:
Warning
Related parameters:
P.0700
Engine type.
P.0704
Can-Bus alarms disable mask.
To disable:
bit 11 of P.0704 on
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only if the board is connected to the engine via the CAN BUS
(P.0700 different from zero). It is activated when the engine signals the battery-charger
alternator failure status over the CAN BUS, but only after the time P.0216 (oil mask) from
engine start has elapsed.
Type:
Alarm
Related parameters:
P.0700
Engine type.
P.0704
Can-Bus alarms disable mask.
To disable:
bit 10 of P.0704 on
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled only if the board is connected to the engine via the CAN BUS
(P.0700 different from zero). It is activated when the engine signals the over speed state over
the CAN BUS.
Type:
Warning
Содержание HS 315
Страница 1: ...File name EAAM058607EN docx Rev 07 Date 25 09 2019 ID Document EAAM0586 Product HS315...
Страница 17: ...Technical Handbook xvii...
Страница 18: ......
Страница 23: ...Technical Handbook 5 Rear view Hall...
Страница 254: ......