116
Technical Handbook
▪
P.0426
(“Days for remote start”).
▪
P.0427
(“Start time for remote start”).
▪
P.0428
(“Stop time for remote start”).
These parameters allow selecting the days of the week and a time slot
within which the working mode switches from AUTO to REMOTE START.
The controller returns to AUTO when interval ends.
o
By means of a proper command via SMS (refer to document [3]). In this case,
the controller shifts to REMOTE START as soon as it receives the SMS and
returns to AUTO when it receives the opposite command.
o
Through a control from the serial ports, using the Modbus HOLDING
REGISTER 101 and 102. These two registers should be written within 5
seconds one from the other (otherwise the control will not work). These
controls can be enabled by a digital input configured with DIF.2706 function -
" Enables the commands by the serial ports ": if this input exists, it should be
active.
▪
Write the password configured with P.0004 parameter in the register
101.
▪
Write the value "13" in the register 102 to switch to REMOTE START,
the value "21" to return to AUTO.
The board records the following events if the working mode changes (if enabled with bit 0 of
P.0441 parameter):
•
EVT.1001
: the new mode is “OFF/RESET”.
•
EVT.1002: the new
mode is “MAN”.
•
EVT.1003: t
he new mode is “AUTO”.
•
EVT.1004
: the new mode is “TEST”.
•
EVT.1005
: the new mode is “REMOTE START”.
The following functions for the configuration of the digital outputs are related to the operation
mode of the board:
•
DOF.3001: the output is activated if the board is in OFF/RESET.
•
DOF.3002: the output is activated if the board is in MAN.
•
DOF.3003: the output is activated if the board is in AUTO.
•
DOF.3004: the output is activated if the board is in TEST.
•
DOF.3005: the output is activated if the board is in REMOTE START.
•
DOF.3011: the output is activated if the board is not in OFF/RESET.
•
DOF.3012: the output is activated if the board is in AUTO, TEST or REMOTE START.
•
DOF.0103 (Logics AND/OR)
o
ST.000: the output is activated if the board is in OFF/RESET.
o
ST.001: the output is activated if the board is in MAN.
o
ST.002: the output is activated if the board is in AUTO.