![Sices HS 315 Скачать руководство пользователя страница 163](http://html1.mh-extra.com/html/sices/hs-315/hs-315_technical-handbook_1263822163.webp)
Technical Handbook 145
Power transferred to the battery during charge cycles (Wh)
No
M.05
Number of discharge cycles
No
M.05
Energy supplied by the battery during charge cycles (Ah)
No
M.05
Power supplied by the battery during charge cycles (Wh)
No
M.05
Estimation of the remaining charge level (Ah)
No
M.02
Estimation of the remaining charge level (%)
No
M.02
Energy transferred to the battery during last BULK (Ah)
No
M.03
Energy transferred to the battery during last ABSORBTION (Ah)
No
M.03
Energy transferred to the battery during last FLOAT (Ah)
No
M.03
Potenza transferred to the battery during last charge (Wh)
No
M.03
Potenza supplied by the battery during last discharge (Wh)
No
M.03
HS315 implements 3 different protections for the current of the plant battery:
•
One warning for high current (W222, parameters P.9721, P.9722, P.9723).
•
One latched warning for maximum current (short circuit) (K224, parameters P.9721,
P.9726, P.9727).
•
One latched warning for time dependent maximum current (K223, parameters P.9724,
P.9725).
HS315 implements 4 different protections for the voltage of the plant battery:
•
One latched warning for minimum voltage (K218, parameters P.9711, P.9712,
P.9713).
•
One warning for low voltage (W219, parameters P.9711, P.9714, P.9715).
•
One warning for high voltage (W220, parameters P.9711, P.9716, P.9717).
•
One latched warning for maximum voltage (K221, parameters P.9711, P.9718,
P.9719).
HS315 implements 4 different protections for the temperature of the plant battery:
•
One latched warning for minimum temperature (K214, parameters P.9701, P.9702,
P.9703).
•
One warning for low temperature (W215, parameters P.9701, P.9704, P.9705).
•
One warning for high temperature (W216, parameters P.9701, P.9706, P.9707).
•
One latched warning for maximum temperature (K217, parameters P.9701, P.9708,
P.9709).
The latched warnings (K214, K217, K218, K221, K223, K224) force the opening of the BCB
circuit breaker (if present).
Содержание HS 315
Страница 1: ...File name EAAM058607EN docx Rev 07 Date 25 09 2019 ID Document EAAM0586 Product HS315...
Страница 17: ...Technical Handbook xvii...
Страница 18: ......
Страница 23: ...Technical Handbook 5 Rear view Hall...
Страница 254: ......