224
Technical Handbook
18
262144
00040000
Tuesday
19
524288
00080000
Wednesday
20
1048576
00100000
Thursday
21
2097152
00200000
Friday
22
4194304
00400000
Saturday
The parameter must be set with the sum of the values of the required days (in hexadecimal
notation).
Selecting a day of the week (Sunday for example),
it is then possible to select if all “Sundays”
in the month must be used or only some of them. Using the parameters of the controller, this
selection is done by means parameter P.1902 (for the calendar 1 or equivalent for other
calendars). This is also a bit-field parameter:
BIT Value
Hexadecimal Occurrence
0
1
00000001
First occurrence
1
2
00000002
Second occurrence
2
4
00000004
Third occurrence
3
8
00000008
Forth occurrence
4
16
00000010
Last occurrence
The parameter must be set with the sum of the values of the required occurrences (in
hexadecimal notation).
Note: for “weekly” calendars, the days of week and their
occurrences in the month are selected by the same parameter, using different bits.
If t
he “occurrence” bits are all “0”, then the selected days of week will be managed in any week
of the month; otherwise they will be managed for the selected occurrences only. The “last”
option is useful because, depending on the month and on the year, a certain day of the week
can be pre
sent 4 or 5 times in a month: using the “last” option you can do an action exactly in
the last occurrence in the month. A typical example is the management of the daylight save
time; in Italy, it is activated on the last Sunday of October, and deactivated on the last Sunday
of March. Those Sundays can be the 4° or the 5° occurrence in the month, depending on the
first day of the month. Using the “last” option, the problem is solved.
Finally, for both “weekly” and “monthly” calendars, it is possible to select a time-slot (valid for
all selected days). The controller will activate the internal bit only inside the selected time-slot.
Using the parameters of the controller, the time-slot can be selected by means P.1903 and
P.1904 (for the calendar 1 or equivalent for other calendars). If those parameters are set with
the same values, the full day is selected. If the start time is lower than the end time, the time-
slot is not across midnight; otherwise, the internal bit is activated after the start time of the
selected days, and it is deactivated after the end time of the day after the selected one.
Using the AND/OR logics, it is possible to activate a digital output into selected days and time-
slot (selected using a calendar):
This is an example for the configuration of the daylight save time for Italy, using calendars 15
and 16:
•
Calendar 15.