The factory-set default functions of the JE outputs on the controller are:
Terminal
Function
JE-1
DOF.1006
– Stop solenoid.
JE-2
DOF.3152
– External horn.
JE-3
DOF.2052
– Coil for opening of LCB
JE-4
DOF.0000
– Not used.
JL-1
DOF.1005
– Command to start the engine.
JL-3
DOF.1003
– Fuel solenoid.
JI-4
DOF.2042
– Coil for opening of BCB.
JI-1
DOF.2032
– Coil for opening of GCB.
JT-1
DOF.0000
– Not used.
JT-2
DOF.0000
– Not used.
JT-3
DOF.0000
– Not used.
JT-4
DOF.0000
– Not used.
The following functions, not directly linked to the operation sequences of the board, are
selectable for any digital output:
•
DOF.0101 -
“Used by PLC”. This function matches the digital output to the PLC
program inside the device; in this way, it is the PLC logic which commands the output,
and not the normal operation logics of the controller. Note: if the PLC program uses
some outputs, but those are not configured with function DOF.0101, the outputs will
not be commanded (but the controller signals this situation with a warning).
•
DOF.0102 -
“Controlled by the serial ports”. The board does not control the output with
its own internal logics, but with the controls it receives through the serial ports.
•
DOF.0103 -
“Logics AND/OR”. See next chapter.
The AND/OR logics are, basically, a list of boolean conditions (true/false, on/off, 1/0), which
can be configured by the operator (programming), which the controller evaluates and the result
of which can be assigned to a digital output or to a virtual digital input (see par. 5.5.3 and par.
5.4.2). For using the AND/OR logics with a digital output, use the DOF.0103 function.
NB: the
AND/OR logics cannot be configured directly from the panel of the controller, but
through a PC equipped with the BoardPrg3 software.