Technical Handbook 91
Page S.14 is hidden if no DITEL modules is present.
When you press the ACK/ENTER button, the controller changes the visualization through
three different modes (LOGICAL STATE, PHYSICAL STATE, BY FUNCTION), showing the
statuses of the digital outputs:
•
LOGICAL STATE
: the output's logic command (active or inactive) used by the
controller in the management of the operating sequence.
•
PHYSICAL STATE
: electrical level (active or inactive, or high or low) present on the
output; this can be the opposite in comparison to the corresponding logic command.
Displayed in negative.
•
BY FUNCTION
: it shows a list of the most common functions really configured for the
digital outputs, each of them with the logical command of the output that manages it
(it is not possible to understand which output manages a specific function, but only the
fact that this output is active or not). If more than six functions must be shown, the
controller shows all them by rotation (every 2 seconds, keep pressed the SHIFT button
to stop the rotation).
Page S.15 (ANALOGUE INPUTS) shows the voltages (Vdc) measured on each JM terminals.
For terminals 2, 3 and 4, it shows also the ohm measured.
Page S.16 (ANALOGUE INPUTS) shows the voltages (Vdc) measured on terminals JQ, JL-2
(emergency stop) and JL-4 (+D).
Page S.17 (ANALOG INPUTS) displays the temperatures measured by DIGRIN and
DITHERM expansion modules. The page is hidden if no such module is configured. The
temperature can be replaced by the following messages:
•
“-----“: when the expansion module does not send the measurement or when the
controller does not receive it.
•
“open”: when the expansion module detects a “broken wire” condition on that sensor.
•
“+over”: when the expansion module measures a too high value (fault).
•
“-over”: when the expansion module measures a too low value (fault).
Page S.18 (ANALOG INPUTS) displays the measures acquired by DIVIT expansion modules
(before applying conversion curves). The page is hidden if no such module is configured. The
measure can be replaced by the following messages:
•
“-----“: when the expansion module does not send the measurement or when the
controller does not receive it.
•
“open”: when the expansion module detects a “broken wire” condition on that sensor.
•
“+over”: when the expansion module measures a too high value (fault).
•
“-over”: when the expansion module measures a too low value (fault).
The S.19 (ANALOG OUTPUTS) page displays the command (as percentage) for the analogue
output of the controller (JR).
Pressing the ENTER button a
“display for function” is shown: the controller shows a list of
functions really associated to the analogue outputs, showing the analogue value of each
function, independently from the output. If more than 6 functions are used for the digital
outputs, the controller shows them all turning (6 at a time) every two seconds: keeping SHIFT
pressed the turning stops.