Technical Handbook 225
o
Select
“weekly” (bit 14 of P.1900 = “1”).
o
Last Sunday of October:
▪
Select
“October” (P.1957 = “0200”).
▪
Select
“Sunday”, “Last” (P.1958 = “00010010”).
o
The activation should happen at 02:00:
▪
Select
“2:00” as start time (P.1959).
▪
Select
“2:01” as end time (P.1960).
•
Calendar 16.
o
Select “weekly” (bit 15 of P.1900 = “1”).
o
Last Sunday of March:
▪
Select
“March” (P.1961 = “0004”).
▪
Select
“Sunday”, “Last” (P.1962 = “00010010”).
o
The activation should happen at 03:00:
▪
Select
“3:00” as start time (P.1963).
▪
Select
“3:01” as end time (P.1964).
The controller provides 4 generic timers fully configurable, that can be used inside the AND/OR
logics to create complex sequential logics. Each timer, in fact, activates/deactivates an internal
bit that can be used by the AND/OR logics.
The four timers are identical.
For each tim
er it is possible to select (by means an AND/OR logic) an “activation condition”
that starts the timer. In the same way, it is possible (but not mandatory) to select (by means
an AND/OR logic) a “reset condition” that resets the timer. When the “reset condition” is true,
the internal bit of the timer is forced to “0”.