Technical Handbook
In the bottom-right corner, the symbol of the battery is shown. This allow the operator to
immediately understand that he/she is looking at battery measurements (there are very similar
pages related to other sources).
This page shows a lot of information regarding the charge/discharge process running on the
plant battery:
•
An indication of the kind of process (charge/discharge).
•
Date and time of the start of the process.
•
Battery voltage (Vdc) at the beginning of the process.
•
Charge level (Ah) at the beginning of the process.
•
Actual charge level (Ah).
•
Power (Wh) transferred from/to the battery since the beginning of the process.
•
Only during charge process: the energy (Ah) transferred to the battery since the
beginning of the current charge phase (BULK, ABSORBTON, FLOAT, FLOAT END).
This page shows the partial (clearable) counters related to charge/discharge cycles. Counters
are provided for the number of cycles, for the transferred power (Wh) and for the transferred
energy (Ah), for both charge and discharge processes. To clear a counter, please follow these
steps:
•
Press the ACK/ENTER button: one counter will be highlighted.
•
Select the required counter using vertical arrows.
•
Keep pressed the buttons ESC/SHIFT + ACK/ENTER until the counter is cleared.
•
Press the ESC/SHIFT button.
In the bottom-right corner, the symbol of the battery is shown. This allow the operator to
immediately understand that he/she is looking at battery measurements (there are very similar
pages related to other sources).
From version 1.08, the counters are protected by the USER level. If a password has been
configured by means parameter P.0001, it is first required to type it (login) into parameter
P.0000, to be able to reset the counters.
This page shows the total (not clearable) counters related to charge/discharge cycles.
Counters are provided for the number of cycles, for the transferred power (Wh) and for the
transferred energy (Ah), for both charge and discharge processes.
In the bottom-right corner, the symbol of the battery is shown. This allow the operator to
immediately understand that he/she is looking at battery measurements (there are very similar
pages related to other sources).
This page shows some information regarding the generator (DC):
•
Voltage (Vdc).
•
Current (Adc, positive if supplied by the generator).
•
Power (kW, positive if supplied by the generator).
In the bottom-right corner, the symbol of the generator is shown. This allow the operator to
immediately understand that he/she is looking at generator measurements (there are very
similar pages related to other sources).
This page is shown only if the controller is configured to acquire the AC voltages of the
generator. It shows: