166
Technical Handbook
It often happens that in the control panel of a generator controlled by HS315 there is no
standard battery charger to keep the engine cranking battery charged. It is normally charged
by the engine
’s battery charger, when the engine is running.
Usually, in this type of system, the engine is started several times a day, so the cranking
battery should remain charged.
If it is discharged, however, you can configure HS315 to start the engine for the sole purpose
of charging the cranking battery; obviously, once the engine is started, the plant battery will
also be charged.
To enable this function, it is necessary to set parameter P.9655: it configures how long (in
minutes) the engine must be kept running to recharge the cranking battery.
If P.9655 is different from zero, when the warning W037 is activated (low cranking battery
voltage, configured with parameters P.0362 and P.0363), HS315 starts the engine and keeps
it running for the time P.9655.
The following events are stored in the archives (if bit 8 of P.0441 is set):
•
EVT.1515: engine started for discharged cranking battery.
•
EVT.1516: engine stopped for recharged cranking battery.