82
Technical Handbook
providing information, no parameter modification will be possible anymore. On the other hand,
knowing the “manufacturer” password will allow to cancel or modify the other passwords.
This procedure will describe the keyboard and display use.
•
Menu 1-SYSTEM allows to show how the controller connects to the engine, to the
generator and to the plant battery. Correct setting of these parameters is paramount
as almost all protection activation thresholds are expressed as a percentage of these
parameters.
•
Working sequence configuration can be modified through the menu 2-SEQUENCE.
In this menu it is possible to set threshold percentages and acquisition times, plus
enabling/disabling operation sequences related functions.
•
Protections management is accessible through the menu 3-PROTECTION. As to this,
it is important to know that, to enable/disable a protection, you may simply modify the
associated time, leaving the threshold unchanged: by setting the time to zero, the
protection is disabled. However, this general rule provides some exceptions. Refer to
the chapter on faults, par. 0, which describes, for each of the faults, the method to
disable it.
•
All operations not related to system, sequence and protections configuration, can be
performed through the menu 4-AUXILIARY FUNCTIONS. This menu contains other
menus used for configuring engine's auxiliary functions and history logs.
•
The menu 5-COMMUNICATIONS allows the configuration of the serial ports, of the
USB port and of the ETHERNET port.
•
The engine menu 7-CAN BUS allows to set the way the controller communicates on
the bus to acquire the engine measures and, should need be, send commands.
The programming is accessible with the controller in any operation state, while parameters
can only be modified, in general, with the controller board in
OFF/RESET
. To enter
programming mode, use
the ▲ and ▼ buttons till the base PROGRAMMING mode (P.03)
screen is displayed.
When in a mode that limits the use of vertical scrolling buttons, it could be necessary to press
one or several times the
ESC
button (this situation can occur when displaying history logs or
during some operations, such as setting the fuel pump control mode).
Then, press
ENTER
to access programming.
The menu or variable selected before the last exit from programming are automatically
displayed when starting the procedure (the main menu is displayed the first time you access).
This is true if the programming procedure has been previously aborted by changing the
operation mode of the controller board in MAN or AUTO or after maximum time with no
programming operation has elapsed or keeping the
ESC
button pressed for more than two
seconds.
P.07 PROGRAMMING |
Main Menu 1/05
1 System
2 Sequence
3 Protections
4 Auxiliary functions