Technical Handbook 175
•
EVT.1437: LCB closed.
•
EVT.1438: LCB opened.
The controller records any
“GCB open” forcing in the events log, if it is enabled with bit 6 of
the P.0441 parameter:
•
EVT.1080: GCB closure inhibition activated (from digital input).
•
EVT.1081: GCB closure inhibition deactivated.
•
EVT.1202: GCB closure inhibition activated (from serial ports / USB / ETHERNET).
•
EVT.1203: GCB closure inhibition activated (because GCB is tripped).
•
EVT.1204: GCB closure inhibition activated (because plant battery is disconnected).
•
EVT.1205: GCB closure inhibition activated (because voltage on bus bars is out of
tolerance).
•
EVT:1221: start inhibition activated (from clock/calendar).
•
EVT:1222: start inhibition deactivated (from clock/calendar).
In addition, the controller makes available the GCB commands and statuses for the AND/OR
logics by means of the following internal statuses:
•
ST.060 -
“GCB status”.
•
ST.061 -
“BCB status”.
•
ST.062 -
“LCB status”.
•
ST.063 -
“ACB status”.
•
ST.064 -
“GCB minimum voltage coil”.
•
ST.065 - "GCB opening pulse".
•
ST.066 - "GCB closure pulse
”.
•
ST.067 - "GCB closure command (stable)
”.
•
ST.068 -
“BCB minimum voltage coil”.
•
ST.069 - "BCB opening pulse".
•
ST.070 - "BCB closure pulse
”.
•
ST.071 - "BCB clos
ure command (stable)”.
•
ST.072 -
“LCB minimum voltage coil”.
•
ST.073 - "LCB opening pulse".
•
ST.074 -
"LCB closure pulse”.
•
ST.075 -
"LCB closure command (stable)”.
•
ST.076 -
“ACB minimum voltage coil”.
•
ST.077 - "ACB opening pulse".
•
ST.078 -
"ACB closure pulse”.