Technical Handbook 193
P.0216
Time mask for engine protections.
P.0339
Low oil pressure threshold.
P.0340
Low oil pressure delay.
P.0700
Engine type.
To disable:
P.0340 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is enabled if the controller acquires the measurement of the oil pressure
(directly from the ECU of the engine or if one of the analogue inputs of the controller is
configured to acquire such measure - function AIF.1000 or AIF.1001 in parameter P.4009 or
equivalent for the other inputs) and if a time other than zero has been set for the protection
(parameter P.0340). It is only enabled if the engine has been started by the controller (if the
command for the fuel solenoid is activated) and is disabled in the engine start/stop phases. It
is activated if the oil pressure remains continuously below or equal to threshold P.0339 for
time P.0340, but only after the time P.0216 (oil mask) from engine start has elapsed (this is to
allow you to ignore the normal status of low pressure, which occurs at start up).
Type:
Alarm
Related parameters:
P.0361
Emergency stop delay.
To disable:
-
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-
This protection is always enabled and cannot be disabled. It is activated if the emergency
shutdown input remains
continuously “not active” for the time set in parameter P.0361 (if the
value set is zero, the alarm is triggered as soon as the input becomes inactive).
Type:
Configurable
Related parameters:
P.0125
Rated engine power.
P.0350
Maximum power threshold.
P.0351
Maximum power delay.
P.0352
Maximum power action.
To disable:
P.0351 =0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
Engine.
This protection is only enabled if the engine has been started by the controller (if the command
for the fuel solenoid is activated), and it is disabled in the engine start/arrest phases. It is
activated if the active power of the generator is positive and remains continuously over the
threshold P.0350 (percentage of the rated power P.0125) for time P.0351. With parameter
P.0352 it is possible to select the protection to be activated.
Type:
Configurable
Related parameters:
P.0438
Interval of days for maintenance.
To disable:
P.0438 = 0
Enabled in:
MAN, AUTO, TEST, REMOTE START
Override:
-