Technical Handbook 61
The configuration parameters are:
Parameter
Description
P.0478
Modbus address
P.0479
Modbus registers order
Link
HS315 is equipped with a RJ45 serial port for data exchange connection via Ethernet network.
For details regarding the network connection and the protocol, refer to document [3].
You can connect the device to a LAN network, or directly to a PC (point to point connection).
The connection allows for the use of the SicesSupervisor SW, configuration through the
BoardPrg3 and of all the available features using the TCP/IP protocol.
The following parameters must be configured:
Parameter Description
Default value
P.0500
IP Address.
192.168.1.1
P.0501
Subnet mask.
255.255.255.0
P.0502
Network Gateway.
0.0.0.0
P.0503
Modbus/TCP Port (0=Modbus/TCP disabled).
502
P.0505
Order of the Modbus registers (Ethernet).
0
P.0508
NTP server port (0=NTP Server disabled).
123
P.0509
NTP server address (0=NTP Server disabled).
0.0.0.0
P.0510
Primary DNS server.
0.0.0.0
P.0511
Secondary DNS server.
0.0.0.0
P.0513
DHCP server port (0=DHCP server disabled).
67
P.0514
DHCP server address (0=DHCP server disabled).
255.255.255.255
To join the device inside a LAN network is necessary to configure the parameters P.0500, P.0501
and P.0502. It is possible to proceed in two different ways:
It is possible to configure the three above mentioned parameters manually, with
congruent values with the network which we are connecting to (the sub-net mask and
the router/gateway are specific of each network, the IP address must be a univocal
address in the network). To proceed this way, it is necessary that the parameter P.0514
is set to 0.0.0.0 or that the parameter P.0513 is set to zero.
It is possible to dynamically get from the network the values for the three above
mentioned parameters. To do so, it is necessary that the controller can connect to a
DHCP server (Dynamic Host Configuration Protocol). To proceed this way, it is
necessary that the parameter P.0514 is set to 255.255.255.255 or that the parameter
P.0513 is set to 67 (67 is the TCP standard port for the DHCP server; if your server use
a different port, set it to P.0513).
Once the controller has valid values for the parameters P500, P501 and P.502, it can be contacted
through TCP-Modbus protocol on the configured IP address and on the configured port with P.053,
i.e. with the supervision SW (SicesSupervisor) and configuration SW (BoardPrg3).